Gateway Start Up
NOTE:
PAGES 12-19 ARE INSTRUCTIONS FOR OPTIONAL PBMI WEBSERVER/BACNET® GATEWAY CARD. THESE INSTRUCTIONS ARE NOT
APPLICABLE FOR SYSTEMS WITH HMI ONLY.
Required Tools & Data
You will need the following tools:
•
The 260MX-S027 Gateway
•
The provided CD-ROM
•
A Working PC (Windows based)
•
An Ethernet Crossover Cable
•
A 12-24 VDC power source (T-strip)
Overview
The 260MX-S027 Gateway device seamlessly connects Modbus RTU Slave devices to a BACnet/IP client. By following this guide, you will
be able to configure the 260MX-S027 Gateway for basic operation. You will set the device’s network settings and parameters to the proper
configuration for initial operation and physically place the device in the network.
Network Connections
The Gateway is shipped out with a Default IP Address of 172.16.3.159 and a Subnet of 255.255.248.0. In order to browse for the gateway’s
main page and begin configuring the gateway, you must change your PC to be on the same network as the gateway.
1. Change the IP Address of your PC to be 172.16.3.158
2. Change the Subnet of your PC to be 255.255.248.0
3. Open IPSetup.exe and browse for the gateway under select a unit.
4. Change the IP Address and Subnet to be on your network.
5. Click Set.
6. Change the PC’s IP Address and Subnet back to its original settings.
7. Browse for the Unit using IPSetup.exe and launch the webpage.