FirstCall™ Liq x Liq Medical Gas Manifold
Operating & Maintenance Manual
Powerex • 150 Production Drive • Harrison, OH 45030 • USA
P 1.888.769.7979 • F 513.367.3125 • www.powerexinc.com
IN599800AV • 15 January 2021
Page 19 of 24
BACnet
Object Name
Object Name Description
FinalLPSI
The displayed pressure value for Final Line Pressure
LefTnkPSI
The displayed pressure value for the left tank
RihTnkPSI
The displayed pressure value for the right tank
ChangePSI
The tank change over pressure value
UOM Type
The unit of measured used in relation to displayed pressure values
FinLinHSP
The High Pressure alarm set point for Final Line Pressure
FinLinLSP
The Low Pressure alarm set point for Final Line Pressure
FinalLoAl
Final Line Pressure High Pressure Alarm Status; 0=No Alarm, 1=Alarm
FinalHiAl
Final Line Pressure Low Pressure Alarm Status; 0=No Alarm, 1=Alarm
LeftEmpty
Left Tank Empty alarm; 0=No Alarm, 1=Alarm
RightEmpt
Right Tank Empty alarm; 0=No Alarm, 1=Alarm
LowBatrAL
PLC/HMI battery alarm status; 0=Normal, 1=Alarm.
(Note: To maintain saved settings, change the battery while the HMI/PLC
is still powered by 24VDC power.)"
AlarmStat
General Fault status; 0=No Alarm, 1=Alarm
EmergnPrs
The displayed pressure value for the emergency tank
EmrgInUse
The emergency tank is in use; 0=No Alarm, 1=Alarm
EmergRsLo
The emergency tank is low in pressure; 0=No Alarm, 1=Alarm
EmrgInUse
The emergency tank is in use; 0=No Alarm, 1=Alarm
EmergRsLo
The emergency tank is low in pressure; 0=No Alarm, 1=Alarm
Appendix A. BACnet Object Names