background image

3

Claw Medical Vacuum Systems

installation

 

 

Disconnect, tag and 

  lockout power before 

attempting to install, service, relocate or perform 
any maintenance.

 

 

Do not lift or move unit without  

  appropriately rated equipment. 

Be sure the unit is securely attached to lifting device used. 
Do not lift unit by holding onto tubes or coolers. Do not use 
pumps to lift other attached equipment.

 

 

Installation of inlet / outlet air  

  plumbing from the system and 

electrical connections must be in accordance with National 
Fire Protection Association (NFPA99) Code Compliance for 
Medical Gas Breathing Air (Level 1).

inSTallaTion SiTe

1.  The vacuum system must be located in a clean, well lit 

and well ventilated area.

2.  The area should be free of excessive dust, toxic or 

flammable gases and moisture.

3.  Never install the vacuum system where the surrounding 

temperature is higher than 104° F or where humidity is 
high.

4.  Clearance must allow for safe, effective inspection and 

maintenance.

5.  If necessary, use metal shims or leveling pads to level the 

system. Never use wood to shim the unit.

6.  The frame is drilled to allow bolting to the floor. Secure 

it as necessary. Rubber composite isolation pads should 
be used to minimize transmission of noise and vibration 
to the building. Additional measures for isolation may 
be required. Drill a hole through the isolation pad and 
center it under the mounting point.

7.  Some systems are built with multiple frames and must be 

installed and the air and electrical connections between 
the frames made at the time of installation. Be sure to 
install the system in the same configuration as shown on 
the system drawing so that the flexible connection hoses 
and electrical lines will fit.

VenTilaTion

1.  If the vacuum system is located in a totally enclosed 

room, an exhaust fan with access to outside air make up 
air must be installed.

2.  Never restrict the cooling fan exhaust air. Maintain the 

clearance listed above.

3.  Never locate the vacuum system where hot exhaust air 

from other heat generating units may be pulled into the 
unit.

WirinG

 

 

Lock out and tag out 

  the electrical supply 

before servicing the equipment. 

 

 

Electrical shock  

  hazard. Make sure 

the system is grounded in accordance with NEC and 
local requirements.

All electrical hook-ups must be performed by a qualified 
electrician. Installations must be in accordance with local and 
national electrical codes. Make sure power supply conductors 
are sized adequately for full system demand.

PiPinG

The system may have temporary shipping supports in 
place. These should be removed when the system piping 
is connected to the building piping. Appropriate supports 
should be added to the system when building tie in is 
completed.
The system has a single point inlet with a flexible connector. 
Each pump is supplied with a flexible connector for tying 
in to the system exhaust. A drip leg should be placed in the 
exhaust as close to the system as possible or multiple drip legs 
can be used at each pump exhaust connection. The drip leg 
must prevent collected condensation from draining back into 
the pump or pumps.
1.  Make sure the piping is lined up without being strained 

or twisted when assembling the piping for the system.

2.  The exhaust piping should be kept as short and have the 

least restriction possible. The flex connector supplied by 
Powerex may be repositioned (changed from vertical to 
horizontal and the elbow turned or removed) if desired 
to achieve a more effective installation to match the field 
installed exhaust piping. Repositioning is desirable if the 
final system plumbing design can be shorter by doing so.

3.  Never use any piping smaller than the pump connection. 

To determine the minimum required pipe size for a 
vacuum system exhaust, calculate the equivalent straight 
length of the run. Never use a pipe size smaller than the 
flex connector supplied by Powerex or smaller than the 
size shown in the 100 foot column on the chart for the 
CFM of the pump. The equivalent straight length is the 
length of all the pipe needed from the flex connector to 
the final outlet plus a factor for each elbow, cross or tee. 
Pipe must be smooth ID. If rough pipe is used, increase by 
one size.

4.  If a grating or grille is used at the end of the exhaust 

pipe, make sure its open area is at least equal to the area 
of the exhaust pipe.

minimUm ClearanCeS

Above

24 inches

Other sides

36 inches

Содержание CVPT Series

Страница 1: ...not avoided WILL result in death or serious injury Warning indicates a potentially hazardous situation which if not avoided COULD result in death or serious injury Caution indicates a potentially haz...

Страница 2: ...eiver Tank The receiver tank in a Powerex Medical Vacuum System is plumbed so that it sees the system vacuum It is not pressurized in normal use and should not be connected to any pressure sources The...

Страница 3: ...ctrical supply before servicing the equipment Electrical shock hazard Make sure the system is grounded in accordance with NEC and local requirements All electrical hook ups must be performed by a qual...

Страница 4: ...f the system extends beyond 600 equivalent straight feet use one size larger pipe Approximate system CFM equals the number of pumps running times CFM in table below Data below is for reference only if...

Страница 5: ...he vacuum level is maintained and the minimum run timer conditions are satisfied 7 Check for excessive vibration unusual noises or leaks during operation If problems are detected shut down the system...

Страница 6: ...maintenance schedule relates to the normal operating conditions If the circumstances and load condition are adverse shorten the interval time and perform maintenance accordingly Maintenance LUBRICATIO...

Страница 7: ...eck drive coupling replace if needed 2 Verify that pump shaft turns freely repair or replace as necessary 3 Check vacuum discharge piping to verify air is being exhausted repair or replace as necessar...

Страница 8: ...ns iii that have been materially modified without the prior written approval of Powerex or iv that experience failures resulting from operation either intentional or otherwise in excess of rated capac...

Отзывы: