background image

2

Claw Medical Vacuum Systems

Components

VaCUUm PUmPS

Powerex medical vacuum systems use electric motor driven 
claw type pumps to create vacuum for the removal of 
unwanted fluids and gases. The pumps remove the gases and 
exhaust them to atmosphere through the exhaust piping 
system.
Systems consist of multiple vacuum pumps that are 
automatically controlled and may be isolated using valves 
for service. One pump is used as the reserve. The control 
system will trigger alarm actions in accordance with NFPA 99 
requirements if the capacity of the reserve pump is needed. 
The control system operates the available pumps in response 
to vacuum demand as determined by the vacuum switches or 
sensor. If needed, the controls will include minimum run timer 
functions to prevent frequent starting and stopping of the 
electric motors.
The vacuum pump assemblies are mounted with vibration 
isolation Each vacuum pump has its own motor. The motors 
are mated to the vacuum pumps by a flange mounting and 
coupling system. Some models include auxiliary cooling fans. 
Maintenance instructions are provided for the vacuum pumps 
and motors in the separate manual. Each vacuum pump has 
an intake assembly that includes 10 micron polyester filters 
for each pump with a small fitting or pipe plug for releasing 
the vacuum and facilitating the removal of the filter covers 
when the pump is isolated the system is still under vacuum. 
Each pump has an in-line check valve and an anti-reverse flow 
valve to prevent them from running backwards when off. An 
inlet screen protects the pump from large particles entering 
the  rotor / vane  area.

reCeiVer Tank

The receiver tank in a Powerex Medical Vacuum System 
is plumbed so that it sees the system vacuum. It is not 
pressurized in normal use and should not be connected to 
any pressure sources. The ASME National Board registered 
air receiver is provided with a manual drain valve as standard 
and optional auto drain and sight tube set ups are available. 
Systems may be built with receivers separately mounted or 
with vacuum pumps and controls integrally mounted.

 

 

Factory installed receiver is  

  used for vacuum capacity only 

and is NOT a collection receiver.

 

 

Never drill holes in,  

  or perform any 

welding on receiver tanks (unless qualified by 
ASME to do so) or use them beyond the rated 
pressure settings. Never mount other machinery or 
equipment on receivers.

STanDarD ConTrol Panel

Built in a Nema 4/12 enclosure, the controls are UL508A 
labeled and NFPA compliant. The panels have a single 
incoming power connection point and two control 
transformers with supplementary fused protected on primary 
and secondary circuits. Systems are designed for automatic 
alternation via PLC control. Systems with two to four motors 
utilize field adjustable vacuum switches. Systems with five 
or more motors utilize a vacuum transducer. Each motor in 
the system is equipped with a magnetic starter and lockable 
motor protector circuit disconnect.
All systems have a 30 minute alternation cycle with 10 minute 
minimum run timers for each pump to prevent short cycling 
and motor damage. Additional features include:
  •  “Reserve Pump in Use” alarm with visual and audible 

indicators.

  •  “Reserve Transformer in Use” visual indicator.
  •  “Power On” light
  •  “Lamp Test” push button
  •  Audible alarm “Acknowledge” push button
  •  Alarm “Reset” push button
  •  Dry contacts on a labeled terminal strip for remote alarm 

connection.

  •  Lighted HOA switch
  •  Hour meter for each motor

Содержание CVPT Series

Страница 1: ...not avoided WILL result in death or serious injury Warning indicates a potentially hazardous situation which if not avoided COULD result in death or serious injury Caution indicates a potentially haz...

Страница 2: ...eiver Tank The receiver tank in a Powerex Medical Vacuum System is plumbed so that it sees the system vacuum It is not pressurized in normal use and should not be connected to any pressure sources The...

Страница 3: ...ctrical supply before servicing the equipment Electrical shock hazard Make sure the system is grounded in accordance with NEC and local requirements All electrical hook ups must be performed by a qual...

Страница 4: ...f the system extends beyond 600 equivalent straight feet use one size larger pipe Approximate system CFM equals the number of pumps running times CFM in table below Data below is for reference only if...

Страница 5: ...he vacuum level is maintained and the minimum run timer conditions are satisfied 7 Check for excessive vibration unusual noises or leaks during operation If problems are detected shut down the system...

Страница 6: ...maintenance schedule relates to the normal operating conditions If the circumstances and load condition are adverse shorten the interval time and perform maintenance accordingly Maintenance LUBRICATIO...

Страница 7: ...eck drive coupling replace if needed 2 Verify that pump shaft turns freely repair or replace as necessary 3 Check vacuum discharge piping to verify air is being exhausted repair or replace as necessar...

Страница 8: ...ns iii that have been materially modified without the prior written approval of Powerex or iv that experience failures resulting from operation either intentional or otherwise in excess of rated capac...

Отзывы: