12
~
=
=
~
Static
Bypass
L N PE
1
A
L N PE
1
L
N
PE
J
L
N
PE
L
N
PE
Bypass
input
Rectifier
input
Fig. 3
~
=
=
~
Static
Bypass
L1 N1 PE
1
1
A
A
L N PE
L2 N2 PE
L1
N1
PE
J
L2
N2
PE
L
N
PE
Fig. 4.
Only required if demanded by that of local wiring rules.
A 1
5KVA 27 10AWG
6KVA 32 10AWG
8KVA 43 8AWG
10KVA 53 8AWG
12KVA 64 8AWG
13
5.4 Default settings at the factory
On the LCD display you will find several of the UPS parameters to select. Default settings
are as follows:
Settings Selection
Factory
default
Output Voltage Setting
208/220/230/240 Vac 230V (FOR HV series)
Input/Bypass Voltage
±10%
+10/-15%
+15/-20%
+10/-15%
Input/Frequency
±2%
±5%
±7%
±5%
HE Mode Setting
On/Off
Off
Free Run Mode
On/Off
On
Bypass Enable/Disable at free run mode Disable/Enable
Disable
Alarm silence
On/Off
Off
Site wiring alarm
Enable/Disable
Disable
External Battery pack setting
0, 1, 2
0
You may change default settings, but we recommend that this is done after installation and
before starting up loads. Read UPS configurations in chapter 7.2 for more information.