Page 42 of 89
(PVI-6000-OUTD-xx-AU Rev:1.0)
5.3.
LED indicators
There are three LEDs at the side of the display: the first LED from the left
(POWER) indicates proper operation of the inverter, the LED in the middle
(FAULT) indicates a fault condition, whereas the LED on the right (GFI) indicates
a ground fault.
1.
The green “Power” LED indicates that AURORA is operating correctly.
This LED flashes upon start-up, during the grid check routine. If a correct grid
voltage is detected and solar radiation is strong enough to start up the unit, the
LED stays on steady. If not so, the LED keeps flashing until solar radiation
becomes strong enough to start up the inverter. In this condition, the display
will read “ Waiting for sun….”
2.
The yellow “FAULT” LED indicates that AURORA has detected a fault
condition. A fault description appears on the display.
3.
The red “GFI” (ground fault) LED indicates that AURORA is detecting a
ground fault in the photovoltaic system (DC side). When this kind of fault is
detected, AURORA immediately disconnects from the grid and the
corresponding fault indication appears on the display. AURORA remains in
this condition until the operator presses the ESC key to re-start the grid
connection sequence. If AURORA does not reconnect to the grid, call service
to have the system troubleshooted.
Fig.19 LED location
Possible LED combinations and their meanings are listed in the following
table.
2
1
3
ESC
UP
DOWN
ENTER
Содержание AURORA PVI-6000-OUTD-AU Series
Страница 16: ...Page 16 of 89 PVI 6000 OUTD xx AU Rev 1 0 Fig 3C Integrated switch and diodes models...
Страница 39: ...Page 39 of 89 PVI 6000 OUTD xx AU Rev 1 0 Fig 18 Data Transmission Options...
Страница 43: ...Page 43 of 89 PVI 6000 OUTD xx AU Rev 1 0 KEY LED on LED blinking LED off Any one of the above conditions...
Страница 70: ...Page 70 of 89 PVI 6000 OUTD xx AU Rev 1 0...
Страница 88: ...Page 88 of 89 PVI 6000 OUTD xx AU Rev 1 0 CERTIFICATE OF CONFORMITY...
Страница 89: ...Page 89 of 89 PVI 6000 OUTD xx AU Rev 1 0...