Page 28 of 89
(PVI-6000-OUTD-xx-AU Rev:1.0)
WARNING:
When selecting the power supply cables for AURORA
connection, please carefully consider nominal operating voltage,
insulation voltage, maximum operating temperature, current density and
flammability rating. All of these values must comply with the maximum
current density ratings required by applicable local rules.
A key consideration in cable selection is cable loss, as exceeding loss will
lead to derating.
The maximum cross-section area allowed for the conductors to be
assembled to the terminal blocks for grid connection is 16 sq mm. The
supplied M32 cable gland accepts wires up to 19 sq mm.
Inverter bottom features (see Fig. 10, from right to left):
2 holes blanked with waterproof caps. Remove the caps to gain access to the
connectors for data serial transfer via RS485 port. One hole is for the input
serial cable and the other for an output cable, if fitted (output cable is required
when several inverters are connected in a daisy-chain configuration, see
Section 6).
Cable gland for AC grid connection
4 pairs of Multi-Contact (MC4) connectors for the two photovoltaic arrays.
Содержание AURORA PVI-6000-OUTD-AU Series
Страница 16: ...Page 16 of 89 PVI 6000 OUTD xx AU Rev 1 0 Fig 3C Integrated switch and diodes models...
Страница 39: ...Page 39 of 89 PVI 6000 OUTD xx AU Rev 1 0 Fig 18 Data Transmission Options...
Страница 43: ...Page 43 of 89 PVI 6000 OUTD xx AU Rev 1 0 KEY LED on LED blinking LED off Any one of the above conditions...
Страница 70: ...Page 70 of 89 PVI 6000 OUTD xx AU Rev 1 0...
Страница 88: ...Page 88 of 89 PVI 6000 OUTD xx AU Rev 1 0 CERTIFICATE OF CONFORMITY...
Страница 89: ...Page 89 of 89 PVI 6000 OUTD xx AU Rev 1 0...