background image

Power-Flo Pumps & Systems • 877-24PUMPS • www.powerflopumps.com

5

Minimum

Submergence Level

Bottom of Feet

9” for HTCE

Receiving Inspection

Upon receiving the pump, it should be 

inspected for damage or shortages.   

If damage has occurred, file a claim 

immediately with the company that 

delivered the pump. If the manual is 

removed from the packaging, do not 

lose or misplace.

Storage

Any product that is stored for a period 

longer than six (6) months from the 

date of purchase should be bench 

tested prior to installation.  A bench 

test consists of,  checking the impeller 

to assure it is free turning and a run 

test to assure the motor (and switch 

if provided) operate properly.  Do not 

pump out of liquid.

Controls

Manual models require a separate 

approved pump control device or panel 

for automatic operation.  Be sure the 

electrical specification of the control 

selected properly match the electrical 

specifications of the pump.

Submergence

The pump should always be operated in 

the submerged condition.  The minimum 

sump liquid level should never be less than 

above the pump’s volute (See Figure 1).

Liquid Level Controls

Typical Discharge Pipe Mounted:

Refer to Figure 2 below which shows a 
typical installation of a 1 phase 115 volt 
pump using a level control mounted 
to the pump with a piggy-back plug.  
The level control should have adequate 
clearance so it cannot hang up in it’s 
swing and that the pump is completely 
submerged when the level control is in 
the “Off” mode.  By adjusting the cord 
tether the control level can be changed.

Automatic:

  Plug float cord into GFI outlet,  then 

 

    plug pump cord into float cord.

Manual: 

    Plug pump cord directly into GFI 

 

    outlet.

Level Control Basic Instructions:

Plug the level control plug into the GFI 

receptacle, then plug the pump into the 

piggy-back plug (See Figure 3).  One cycle 

of operation should be observed, so that 

any potential problems can be corrected.

It is recommended that the level control 

float should be set to insure that the liquid 

in the sump never drops below the top 

of the motor housing or a minimum level 

of 6 inches (9inches on HTCE) above the 

basin floor.

Installation

These pumps are recommended for 
use in a sump or basin. The sump 

or  basin shall be sealed and vented 

in accordance with local plumbing 

codes. 

This pump is designed to pump 

effluent or wastewater, nonexplosive 

and noncorrosive liquids and shall 

NOT be installed in locations classified 

as hazardous in accordance with the 

National Electrical Code (NEC) ANSI/

NFPA 70 or Canadian Electric Code 

(CEC).

 The pump should never be 

installed in a trench, ditch, or hole with 

a dirt bottom. The legs will sink into 

the dirt and the suction will become 

plugged.

Figure 1

Receiving & Installation

Recommended

Submergence Level

Typical Installation with Wide Angle 

Level Control

Figure 2

Figure 3

PFS411HTCE-2    

 

 

          Submersible Effluent, Sump & Sewage Pumps

Содержание PFS411HTCE-2 Series

Страница 1: ...o Pumps Systems 877 24PUMPS www powerflopumps com 0 4 HP 1750 RPM 60 Hz Submersible Effluent Sump Sewage Pump High Temperature ISP No PFS411HTCE 2 9 2020 INSTALLATION SERVICE PARTS MANUAL Series PFS41...

Страница 2: ...not insert fingers in pump with power connected Always wear eye protection when working on pumps Do not wear loose clothing that may become entangled in moving parts Pumps build up heat and pressure d...

Страница 3: ...Volt Pressure Grommet for Sealing and Strain Relief MOTOR Oil Filled Squirrel Cage Induction Class H Insulation Vacuum Pressure Impregnated VPI SINGLE PHASE Permanent Split Capacitor PSC Includes Over...

Страница 4: ...Power Flo Pumps Systems 877 24PUMPS www powerflopumps com 4 Dimensions Performance High Temp PFS411HTCE 2 Submersible Effluent Sump Sewage Pumps...

Страница 5: ...adequate clearance so it cannot hang up in it s swing and that the pump is completely submerged when the level control is in the Off mode By adjusting the cord tether the control level can be changed...

Страница 6: ...is required consult a qualified electrician for proper wire size Pre Operation 1 Check Voltage and Phase Compare the voltage and phase information stamped on the pump name plate 2 Check Pump Rotation...

Страница 7: ...ure and remove the gauge assembly Replace oil Leek must be located and repaired if pressure does not hold Pressure builds up extremely fast increase pressure by TAPPING air nozzle Too much pressure wi...

Страница 8: ...g a seal tool being carefull not to damage seal face Make sure spring is seated in retaining ring and spring is lined up on rotating member and not cocked or resting on bellows tail Motor 5 Slide roto...

Страница 9: ...www powerflopumps com 9 Repair Parts For Repair Part Please supply Model Number and MFG Date as shown on Name Plate and Part Description and Part Number as shown on Parts List Figure 5 PFS411HTCE 2 Su...

Страница 10: ...andle 15 1 Power Cord 15 Ft 16 3c SJOOW includes 15A 15G PF100502K 15A 1 Terminal Pin Holder 15B 1 Epoxy 15C 1 Ring 15D 1 Nylon GF Housing 15E 1 Nut Torque to 17 5 Ft Lbs 15F 1 Kellum Grip Cable 15G 1...

Страница 11: ...quired Consult the factory Disconnect unit electrically Remove the pump from the basin Detach the pump base and clean the area around the impeller Rotate impeller by hand Reassemble and reinstall Pump...

Страница 12: ...f God that has not been installed operated or maintained in accordance with Manufacturer s installation instructions that has been exposed to outside substances including but not limited to the follow...

Отзывы: