POWER ELECTRONICS
SD750FR
RECEPTION, HANDLING AND TRANSPORTATION
27
Extended storage
If the equipment is stored for an extended period (more than 6 months) before installation for an
undefined date, new considerations should be taken, in addition to the recommendations in section
“Standard storage”.
•
The drive must be stored in its original packaging.
•
Draining bags shall be included inside the packaging to prevent moisture from damaging the
equipment or its electronic components. These shall be replaced when storage conditions
require it.
•
Periodic inspections of the internal equipment status should be performed when possible.
Proper internal cleanness must also be checked.
•
To prevent deterioration of the capacitors, connect the equipment without load for 30-60
minutes once a year.
•
Before commissioning, it is recommended to follow the instructions to connect power supply
safely to the equipment. Please refer to document
VFIC001
.
Handling and Transportation
Only the transport methods described in this document or in the delivery notes are permissible. Any other
transport method or system could damage the unit.
SD750FR is delivered vertically. Frames 1 and 2 are delivered in a cardboard box. From frame 3 they
are delivered fastened to a wooden pallet. Frames 3 and 4 are covered with a cardboard box and from
frames 5 with a wooden box. Depending on the method of transportation, the drive is supplied wrapped
to be protected against dust. Place the entire pallet as close as possible to the installation site before
removing the wooden box to prevent damage to the drive during transportation.
It is mandatory to carry the drive with a pallet truck, a forklift truck, or a crane, taking into account the
load distribution and its center of gravity. Check the size and weight of the VFD to choose a proper
equipment that can lift a higher weight.
Remove the drive packaging carefully (do not use sharp tools). After removing the packaging, please
check the material inside. Verify that the number of items included in the package is in accordance with
the inventory. In case of receiving spare parts with the product, please separate it and store it in a safe
place. It should not be exposed to vibrations, falls or moisture.
Содержание SD750FR
Страница 1: ...SD750FR HARDWARE AND INSTALLATION MANUAL 4Q REGENERATIVE ACTIVE FRONT END DRIVE...
Страница 2: ......
Страница 54: ...SD750FR POWER ELECTRONICS 52 POWER CONNECTION EN Connections for frame 6...
Страница 55: ...POWER ELECTRONICS SD750FR POWER CONNECTION 53 Connections for frame 7...
Страница 56: ...SD750FR POWER ELECTRONICS 54 POWER CONNECTION EN Connections for frame 8...
Страница 79: ......
Страница 80: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT...