POWER ELECTRONICS
SD750FR
POWER CONNECTION
47
It is recommended to use shielded cable for control signals and to follow recommendations included in
section
“Wiring recommendations”.
CAUTION
Select communication and control system according to the drive EMC environment.
Otherwise,
systems could suffer from interferences due to a low EMS level.
Protections
Short circuit
The SD750FR includes from frame 5 to 8 ultra-fast input protection fuses as standard. Frame 5 includes
one fuse per phase with a rated current that depends on the drive’s nominal current. From frame 6
upwards, the fuses per phase depend on the number of modules (frame 5) interconnected. The main
characteristics of these fuses are shown in the following table.
FUSE CHARACTERISTICS
In (A)
Ic @ Un
(A)
I
2
t @
1ms I
2
t
p
(A²s)
I
2
t @ Un
(A²s)
Un (V)
Manufacturer
Model
250A
200kA
4700
25000
690VAC
WESTCODE
069UR1S0250B
350A
200kA
10500
55000
690VAC
WESTCODE
069UR1S0350B
However, it is not recommended to install the drive at points where the short-circuit current available is
higher than 200kA. If necessary, install general fuses with a greater breaking capacity and with fastest
overcurrent capacity.
Содержание SD750FR
Страница 1: ...SD750FR HARDWARE AND INSTALLATION MANUAL 4Q REGENERATIVE ACTIVE FRONT END DRIVE...
Страница 2: ......
Страница 54: ...SD750FR POWER ELECTRONICS 52 POWER CONNECTION EN Connections for frame 6...
Страница 55: ...POWER ELECTRONICS SD750FR POWER CONNECTION 53 Connections for frame 7...
Страница 56: ...SD750FR POWER ELECTRONICS 54 POWER CONNECTION EN Connections for frame 8...
Страница 79: ......
Страница 80: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT...