SD750
POWER ELECTRONICS
22
ETHERNET/IP PROTOCOL
Attribute
ID
Name
Data type
Units
Description
Services
17
Output voltage
INT
V
Output voltage
Get
18
AccelTime
UINT
[ms]
Acceleration time
Get/Set
19
DecelTime
UINT
[ms]
Deceleration time
Get/Set
20
LowSpdLimit
UINT
rpm
Minimum speed limit
Get/Set
21
HighSpdLimit
UINT
rpm
Maximum speed limit
Get/Set
22
SpeedScale
INT
-
Speed scaling factor
1
-
Scaled speed = rpm / 2^SpeedScale
-
Range: -128 to 127
Get/Set
23
CurrentScale
INT
-
Current scaling factor
-
Scaled current = A / 2^CurrentScale
-
Range: -128 to 127
Get/Set
24
TorqueScale
INT
-
Torque scaling factor
-
Scaled torque= Nm / 2^TorqueScale
-
Range: -128 to 127
Get/Set
25
ProcessScale
INT
-
Process scaling factor
-
Scaled process = % / 2^ProcessScale
-
Range: -128 to 127
Get/Set
26
PowerScale
INT
-
-
Scaled power = W / 2^PowerScale
-
Range: -128 to 127
Get/Set
27
VoltageScale
INT
-
Voltage scaling factor
-
Scaled voltage = V / 2^VoltageScale
-
Range: -128 to 127
Get/Set
28
TimeScale
INT
-
Time scaling factor
-
Scaled time = ms / 2^TimeScale
-
Range: -128 to 127
Get/Set
29
RefFromNet
BOOL
-
Status of torque/speed reference
0: Local torque/speed reference
1: Torque/speed reference from network
Get
30
ProcFromNet
BOOL
-
Status of process control reference
Get
Object Custom Modbus
This is a customized object, with a
single instance
. Each attribute represents a custom Modbus value
(1 ... 32). Attributes 1 to 16 are read-only for the master (Get) and from 17 to 32 are write-only (Set).
Note
: For the correct operation of this object, user must configure the custom parameters in groups
G21.3.2 and G21.3.3 of the SD750. Attributes of the object Custom Modbus make use of these
parameters so the user is capable of configuring them with the variables from the SD750 drive that are
most relevant to him.
Attribute ID
Name
Data type
1
Modbus Var 1
UINT
2
Modbus Var 2
UINT
3
Modbus Var 3
UINT
4
Modbus Var 4
UINT
5
Modbus Var 5
UINT
6
Modbus Var 6
UINT
7
Modbus Var 7
UINT
8
Modbus Var 8
UINT
1
Note:
Attributes
7 to 21
(both included) have a scale 2^scale factor. This scale factor is taken from attributes 22 to 28,
but if their value is set to 0 no scaling will be applied.
Содержание SD750 Series
Страница 1: ...SD750 LOW VOLTAGE VARIABLE SPEED DRIVE ACCESSORIES MANUAL ETHERNET IP BOARD...
Страница 2: ......
Страница 3: ...Accessories Manual Ethernet IP board Edition February 2022 SD75MA01CI Rev C...
Страница 40: ...SD750 POWER ELECTRONICS 38 FAULTS AND WARNINGS LIST...
Страница 41: ......
Страница 42: ...24H TECHNICAL ASSISTANCE 365 DAYS A YEAR FIND YOUR NEAREST DELEGATION POWER ELECTRONICS COM CONTACT...