POWER ELECTRONICS
SD700FL SERIES
CONTROL CONNECTION
65
7.5.2.
Safety Integrity Level SIL1- PLc
This connection scheme provides an easy and cost effective solution for installations that not
require the highest safety level requirements. In this case, the two NC contacts from the external
push button are directly connected to the optional STO board. As the previous solutions, the
operator pressing sensor will deactivates the IGBT switching of the inverter bridge through two
independent channels, disconnecting the motor power supply and avoiding any possible
unexpected restart. The monitoring terminals will not be connected.
Figure 7.11 Emergency Stop Push button connection scheme
– SIL 1 -PLe
X1.19 and X1.20 terminals can be used for other purpose depending on the inverter applications
(frequency reference performed by an external potentiometer, analogue feedback etc…). In order
to avoid the multiple cable connection in a single terminal (X1.19, X1.20), it is recommended to
add additional external terminals to distribute the power supply.
CAUTION
According to EN 60204-1, automatic restart is not allowed after an emergency stop. For this
reason, the machine control must prevent an automatic start after emergency stop.
Содержание SD700FL Series
Страница 1: ...LowHarmonicsNotchFilter Hardware and Installation Manual FL ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Hardware and Installation Manual Edition December 2012 SD7FLMTHW02AI Rev A ...
Страница 4: ...SD700FL SERIES POWER ELECTRONICS 2 ...
Страница 6: ...SD700FL SERIES POWER ELECTRONICS 4 Revisions Date Revision Description 14 12 2012 A First edition ...
Страница 92: ...SD700FL SERIES POWER ELECTRONICS 90 ...
Страница 95: ...www power electronics com ...