POWER ELECTRONICS
SD700FL SERIES
POWER CONNECTION
35
6.3.2.
Recommended Cable Section for 690VAC
FRAME
CODE
I(A)
Rated
Power (kW)
at 690VAC
Recommended
Cable Section
per Phase
Recommended
Cable Section
for Earth Wire
AWG /
kcmil
mm²
AWG /
kcmil
mm²
3
SD7FL0052 6X Y
52
45
3 – 1
16 – 25
3 – 1
16 – 25
SD7FL0062 6X Y
62
55
3 – 1
16 – 25
3 – 1
16 – 25
4
SD7FL0080 6X Y
80
75
100
95
100
95
SD7FL0105 6X Y
105
90
2/0 – 4/0
50 – 95
2/0 – 4/0
50 – 95
5
SD7FL0130 6X Y
130
110
3/0 – 300
70 – 120
3/0 – 300
70 – 120
SD7FL0150 6X Y
150
132
3/0 – 300
70 – 120
3/0 – 300
70 – 120
SD7FL0170 6X Y
170
160
3/0 – 300
95 – 150
3/0 – 300
95 – 150
6
SD7FL0210 6X Y
210
200
300 – 500
120 – 240
300 – 500
120 – 240
SD7FL0260 6X Y
260
250
2 x 300
2 x 150
2 x 300
2 x 150
SD7FL0320 6X Y
320
315
2 x 500
2 x 185
2 x 500
2 x 185
7
SD7FL0385 6X Y
385
355
2 x 500
2 x 240
2 x 500
2 x 240
SD7FL0460 6X Y
460
450
2 x 500
2 x 240
2 x 500
2 x 240
8
SD7FL0550 6X Y
550
500
2 x 500
2 x 240
2 x 500
2 x 240
SD7FL0660 6X Y
660
630
3 x 500
3 x 240
3 x 500
3 x 240
9
SD7FL0750 6X Y
750
710
4 x 500
4 x 240
4 x 500
4 x 240
SD7FL0840 6X Y
840
800
4 x 500
4 x 240
4 x 500
4 x 240
SD7FL0950 6X Y
950
900
4 x 500
4 x 240
4 x 500
4 x 240
10
SD7FL1140 6X Y
1140
1000
6 x 500
6 x 240
6 x 500
6 x 240
SD7FL1270 6X Y
1270
1200
6 x 500
6 x 240
6 x 500
6 x 240
SD7FL1420 6X Y
1420
1400
7 x 500
7 x 240
7 x 500
7 x 240
11
SD7FL1500 6X Y
1500
1500
8 x 500
8 x 240
8 x 500
8 x 240
SD7FL1800 6X Y
1800
1800
8 x 500
8 x 240
8 x 500
8 x 240
Note:
Cable must be suitable for a permanent Tª >75ºC. Use 600V cables for up to 500Vac rated
voltage. For 690Vac phase to phase rated equipment use 1kV cables.
However, this is a
recommendation; ensure follow local regulation.
6.4.
Ground connection
Before connecting the power conductors, be sure that the chassis of the filter, drive and the adjoining
cabinets are connected to ground through the dedicated (PE) terminals. They are situated at both sides
of the bottom metallic walls of the cabinets and they are labelled with the appropriate ground connection.
Check section
“6.9 and 6.10”.
Motor
‟s chassis grounding must be connected to the drive. In other words, connect the motor‟s ground
conductor
to the PE output terminal of the drive and not to the installation‟s ground. We recommend that
the cross section of the
motor‟s ground conductor (PE) should have at least the cross section of the
active conductor (U, V, W). Should be installed following the recommendations indicated in
section “6.3
Power Connection and wiring”.
When connecting the earth, ensure that all connected terminal lugs are securely tight and protected from
mechanical forces. The tightening torque in case of M10 PE terminals is 40Nm.
CAUTION
For safety reasons it is determinant to measure the grounding resistance of the plant itself.
This
must be established before the first start up of the plant and with the drive disconnected.
It is responsibility of the installer to provide the adequate number, type and cross section
grounding conductor
alongside with the characteristics of the drive used and of the Plant in order to
minimize the grounding resistance, that comply with the local and national regulation.
Содержание SD700FL Series
Страница 1: ...LowHarmonicsNotchFilter Hardware and Installation Manual FL ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Hardware and Installation Manual Edition December 2012 SD7FLMTHW02AI Rev A ...
Страница 4: ...SD700FL SERIES POWER ELECTRONICS 2 ...
Страница 6: ...SD700FL SERIES POWER ELECTRONICS 4 Revisions Date Revision Description 14 12 2012 A First edition ...
Страница 92: ...SD700FL SERIES POWER ELECTRONICS 90 ...
Страница 95: ...www power electronics com ...