SD700FL SERIES
POWER ELECTRONICS
82
MAINTENANCE
11.
MAINTENANCE
SD700FL drives consist of advanced semiconductor devices. Temperature, humidity, vibration and
deteriorated components can reduce their efficiency. To avoid any possible irregularity we recommend
making periodic inspections.
11.1.
Warnings
Be sure to remove the input power while performing maintenance.
Be sure to perform maintenance after checking the DC Link capacitor has discharged. Check
that the voltage between terHVDC and -HVDC is below DC 30V. The bus capacitors
in the drive main circuit can still be charged even after the power is turned off.
The correct output voltage of the drive can only be measured by using an RMS voltage meter.
Others voltage meters, including digital voltage meters, are likely to display incorrect values
caused by the high frequency PWM output voltage of the drive.
11.2.
Routine Inspection
Be sure to check the following points before handling the drive:
Installation site conditions.
Drive cooling system conditions.
Excessive vibrations or noise in the motor.
Excessive overheating.
Normal output current value on the monitor.
In
sp
ec
tio
n
si
te
Inspection
element
Inspection
Period
Inspection method
Criterion
Instrument of
Measurement
M
on
th
ly
1
ye
ar
2
ye
ar
s
All
Ambient
conditions
Are there dust particles?
Are the ambient
temperature and the
humidity within
specification?
o
Visual check
Temperature:
-30 to +50 ( or 40ºC)
Humidity: below 95% non-
condensing.
Thermometer,
Hygrometer,
Recorder.
Module
Are there any abnormal
noises or oscillations?
o
Visual and audible.
There are no anomalies.
Input power
Is the input power to the
main circuit correct?
o
Measure the voltage between
terminals L1, L2, L3 and PE.
Digital
multimeter.
Tester.
Power
connections
Are the Power terminals
correctly fastened?
o
Measure the temperature and
torque of the power
connections
Fasten the bolts again one
week after its start-up.
Check that the
temperature is
homogeneous and below
70ºC
Infrared
thermometer ,
Torque key
M
ai
n
ci
rc
ui
t
Conductor/
Cable
Is the conductor
corroded?
Is the sheathing of the
cable damaged?
o
o
Visual check.
No anomaly.
Terminal
Is any damage visible?
o
Visual check.
No anomaly.
IGBT's module
Diodes module
and Rectifier
Check the resistance
value between each one
of the terminals
o
Disconnect the cables of the
inverter and measure the
resistance value between:
L1, L2, L3,
VDC+, VDC-
and
U, V, W
VDC+, VDC-
with a tester > 10k
Digital
multimeter.
Analogue tester.
Содержание SD700FL Series
Страница 1: ...LowHarmonicsNotchFilter Hardware and Installation Manual FL ...
Страница 2: ......
Страница 3: ...Variable Speed Drive Hardware and Installation Manual Edition December 2012 SD7FLMTHW02AI Rev A ...
Страница 4: ...SD700FL SERIES POWER ELECTRONICS 2 ...
Страница 6: ...SD700FL SERIES POWER ELECTRONICS 4 Revisions Date Revision Description 14 12 2012 A First edition ...
Страница 92: ...SD700FL SERIES POWER ELECTRONICS 90 ...
Страница 95: ...www power electronics com ...