POWER ELECTRONICS
SD300 SERIES
POWER CONNECTION
37
Recommended Cable Section
Model
Screw
Torque
[1]
[Kgf * cm / Nm]
Wire
[2]
mm²
AWG
R, S, T
U, V, W
R, S, T
U, V, W
230V 1-phase
0.4 kW
M3.5
(1/8
“)
2.1 ~ 6.1 / 0.2 ~ 0.6
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
M4
(1/8“)
3.5
3.5
12
12
230V 3-phase
0.4 kW
M3.5
(1/8“)
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
3.7 kW
M4
(1/8“)
3.5
3.5
12
12
4 kW
5.5 kW
6
6
10
10
7.5 kW
11 kW
M5
(3/16“)
4.0 ~ 10.2 / 0.4 ~ 1.0
10
10
8
8
15 kW
16
16
6
6
400V 3-phase
0.4 kW
M3.5
(1/8“)
2.1 ~ 6.1 / 0.2 ~ 0.6
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
3.7 kW
M4
(1/8“)
4 kW
5.5 kW
2.5
2.5
14
14
7.5 kW
4
4
12
12
11 kW
M5
(3/16“)
4.0 ~ 10.2 / 0.4 ~ 1.0
15 kW
6
6
10
10
18.5 kW
10
10
8
8
22 kW
[1] Use only the specified torque on the screws, otherwise damage could occur. Loose screws can cause overheating and
damage.
[2]
Wires must permanently support 600V and Tª >75ºC.
Ground Connection
Before connecting the power conductors, make sure that the chassis of the drive and the adjoining cabinets
are connected to ground through the dedicated (PE) terminals. The PE terminals are located in the bottom
part of the drive and labelled with the appropriate ground connection.
Figure 7.10 PE terminals location
Содержание SD300146
Страница 1: ...VARIABLE SPEED DRIVE Variable Speed Drive Hardware and Installation Manual...
Страница 2: ......
Страница 3: ...Variable Speed Drive Hardware and Installation Manual Edition February 2017 SD30MTHW01CI Rev C...
Страница 4: ...SD300 SERIES POWER ELECTRONICS 2 SAFETY SYMBOLS...
Страница 62: ...SD300 SERIES POWER ELECTRONICS 60...
Страница 65: ...www power electronics com...