Powered by Safety
®
16
Installation
01.4IB.48040C
BriteSpot™ BSG3
Figure 14 Secure Probe by Tightening Allen Key
6. Validate that the probe is properly secured
into the lug by giving a gentle tug. At this
point the joint can be carefully dressed, if
required, while ensuring the probe is not
abused.
Figure 15 Correctly Installed Probe and Lug
c. r
Oute
f
iBer
-O
ptic
p
rOBe
Proper routing of the probe is important to
facilitate proper installation of the BriteSpot™.
The optical fiber has some general guidelines
that must be followed during installation:
1. Ensure that bend radii are greater than
1.3 cm (½”). Bends smaller than this will
cause a loss in optical signal.
2. Keep exposed sections of the fiber away
from excessive temperatures. The tip has
been designed to allow for temperatures
up to 120˚C (248˚F) and the fiber for
temperatures up to 100˚C (212˚F).
Temperatures in excess of these could
cause premature failure of the fiber.
Figure 16 Fiber Limitations
R>1/2"
R
Sensor Tip
MAX 120°C
Fiber
MAX 100°C