6
SITE REQUIREMENTS - Page 6
Figure 3 THE SITING OF BALANCED FLUE TERMINAL BOILER
POSITION
MINIMUM
DISTANCE
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY OTHER
VENTILATION OPENING
BELOW GUTTER, DRAIN/SOIL PIPE
BELOW EAVES
BELOW A BALCONY OR CAR PORT
ROOF
FROM VERTICAL DRAIN PIPES AND
SOIL PIPES
FROM INTERNAL OR EXTERNAL
CORNERS
ABOVE ADJACENT GROUND OR
BALCONY LEVEL
FROM A SURFACE FACING THE
TERMINAL
FACING TERMINALS
FROM OPENING (DOOR/WINDOW) IN
CARPORT INTO DWELLING
VERTICALLY FROM A TERMINAL ON
THE SAME WALL
HORIZONTALLY FROM A TERMINAL
ON THE SAME WALL
ADJACENT TO OPENING
mm
300
300
300
600
75
600
300
600
600
1200
1500
300
300
ELECTRICITY SUPPLY
A 240 volts
—
50Hz., single phase electricity supply fused at
3A must be provided in accordance with the latest edition of
the lEE wiring regulations and any other local regulations
that may apply. The current rating of the wiring to the boiler
must exceed 3 amperes and have a cross sectional area of
at least 0.75mm
2
in accordance with BS6500 1990 Table
16. The method of connection to the electricity supply
MUST
facilitate complete isolation of the appliance, preferably by
the use of a fused three-pin plug and unswitched,
shuttered socket outlet, both complying with the
requirements of BS1363. Alternatively, connection may be
made via a fused double pole isolator having a contact
separation of 3mm in all poles and serving the appliance
and system controls only.
TECHNICAL DATA - Page 6
Maximum Working Head
30.5m (l00ft)
Minimum Working Head (Fully pumped systems)
150mm (6in)
Minimum Circulating Head (Gravity systems)
1.2m (4ft)
Gas Supply Pressure
20 mbar
Maximum Flow Temperature
82 º C
Electricity Supply
240v
-
50Hz fused at 3A
Flow/Return Connection
28mm copper
Gas Supply Connection
Rc, ½ (½
in BSP Female)
Power Consumption
20 watts
30 & 40 model
50 & 60 model
Water Content
1.8 litre
2.5 litre
0.4 gal
0.55 gal
Appliance Weight
-
installed
39.2 kg
46.8 kg
86.0 lbs
103.3 lbs
Appliance Weight
-
lift
31.0 kg
38.5 kg
68.0 lbs
85.0 lbs