Publication No. 5102977
29
4.7
Combustion Chamber Insulation
•
Gain General Access - See 4.1
1. Remove the burner/gas valve assembly -
See 4.6.
2. Remove combustion chamber front cover -
2 screws
Note: To avoid release of dust and fibrous
material the insulation material should be
dampened before removal.
3. Push both sides of the combustion chamber
inwards at the top to unclip and pull forwards
out from the boiler. Replace insulation pieces
as required. On 40 model carefully bend
securing tabs out sufficiently to remove
insulation, DO NOT overbend. On 50 to 100
models replace any securing clip if damaged.
4. Re-assemble in reverse order.
4.8
Fan & Fluehood
•
Gain General Access - See 4.1
1. Disconnect the tube from the fan pressure
sensing point on the front of the fan housing
- note how it fits.
2. Disconnect the three wires from the fan
motor.
3. Remove the securing screw and carefully
pull the fan down and away from the boiler.
4. Remove the fluehood - 2 screws and
withdraw it from the boiler.
5.
Fluehood: On re-assembly check the seal
on the fluehood and replace if damaged and
ensure that the fluehood locates under the
bracket at the rear of the chassis. .
6.
Fan: On re-assembly check the seal on the
fan inlet and replace if damaged, ensure that
the rubber seal around the fan outlet is
located correctly into the base of the flue
elbow.
7. Re-assemble in reverse order.
4.9
Products Discharge Safety Device
- TTB
(CFL Models Only)
•
Gain General Access - See 4.1
1. Note how it fits then remove the sensor. re-
fit in reverse order.
2. If the device is disturbed during routine
servicing an operational check should be
carried out.
3. This component should only be replaced by
the manufacturers original part.
Service & Replacement of Parts
Fig. 28
Fan Pressure
Sensing Point
Insulation
Combustion Chamber Insulation (40 Model)
Insulation
Securing Tabs
Insulation
Securing Tabs
CON0097A
Содержание Kingfisher Mf CFL40 - 100
Страница 13: ...Publication No 5102977 13 CON0093B Installation Requirements Fig 8 Fig 7 ...
Страница 14: ...Publication No 5102977 14 Installation Requirements Fig 9 Fig 10 ...
Страница 30: ...Publication No 5102977 30 5 Wiring Diagrams Functional Wiring Diagram Fig 29 Air Pressure Switch CON0089A ...
Страница 31: ...Publication No 5102977 31 Fig 30 Pictorial Wiring Diagram CON0082B T T B CFL Models Only ...
Страница 34: ...Publication No 5102977 34 Fault Finding ...
Страница 35: ...Publication No 5102977 35 Fault Finding ...