2-13
PFC-6800 • 5403602 • Rev B • 2/13
SLC #___ Current Draw Worksheet for SLCE-127s
(Complete one for each configured SLCE-127)
Device Type
Qty
Standby
(mA)
Total
Standby
(mA)
Alarm
(mA)
Total
Alarm
(mA)
SLCe-127 Main Board
1
60
60
Analog photo smoke detector (PSA)
0.325
0.325
Analog photo DUCT smoke detector (DSA)
0.325
0.325
Analog photo smoke / fixed heat detector (PSHA)
0.325
0.325
Analog fixed heat detector (FHA)
0.325
0.325
Analog combo heat detector (RHA)
0.325
0.325
Conventional initiating zone module - 4 inch mount (CIZM-4) *Note 1
0.325
1.000
Miniature contact module (MCM)
0.325
0.325
Single contact module - 4 inch mount (SCM-4)
0.325
1.000
Dual contact module - 4 inch mount (DCM-4)
0.325
1.000
Monitored output module - 4 inch mount (MOM-4) *Note 2
0.325
1.000
Twin relay module - 4 inch mount (TRM-4)
0.325
1.000
Short circuit isolator (SCI)
0.325
2.34
Analog sounder base (ASB)
0.325
0.325
Analog relay base (ARB)
0.325
0.325
Isolator base (AIB)
0.325
2.34
SLC alarm LeD Current
n/a
n/a
n/a
27.0
SLC Standby
Current
SLC Alarm
Current
* Note 1: CIZM requires 24vDC power source. Standby current Style D = 4.90 mA, Style B (8.5 mA). Alarm Current = 50.0 mA
* Note 2: MOM requires 24vDC power source. Standby current = 1.60 mA. Alarm Current = 1.60 mA
* Note 3: ASB requires 24vDC power source. Standby current = 5 mA. Alarm Current = 100 mA
* Note 4: ARB requires 24vDC power source. Standby current = 5 mA. Alarm Current = 50 mA