Setting Addresses
A SPG-1000 address is set by
dip switch S1
. The address must be set in the range of one (1) to thirty-one (1–31) to be recognized
by the panel.
(Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)
SPG-1000 Back Panel View Showing Dip Switch Location
Figure 52.
SLCE-127 Installation
The panel supports up to seven (7) SLCe-127s. The SLCe-127 utilizes a signaling line circuit for communication to various
sensors and modules. The system polls each loop between every 4–5 seconds. The SLCe-127 supports a maximum of 127
addressable devices configured in any combination of smoke sensors, heat detectors, input modules or output modules.
SLCE-127 Wiring
Outputs are supervised and regulated.
y
y
Circuits are low voltage and power limited.
y
y
All wiring must be separated by at least 0.25 inches and the wire insulation must be for the higher voltage.
y
y
The SLCe-127 is supplied with a mounting bracket which allows it to be mounted into a compatible fire enclosure. Please refer to
the figures shown below:
Example of the SLCE-127
Figure 53.
DWG #602-16
P-Link
Connections
Dip Switches
DWG #608-25
S1