2-4
PFC-6800 • 5403602 • Rev B • 2/13
Section 2: Before You Start Installation
This section addresses information that will help you in completing a successful installation, such as the PFC-6800 cabinet layout,
specifications, environmental considerations, and calculating the battery circuit and SLC current draw requirements.
System Specifications
Cabinet Description
Sixteen (16) gauge sheet steel with hinged, removable locked door
y
y
enclosure dimensions – 26" x 17.6" x 3.75"
y
y
Visual Indicators
LCD (4 x 40 alphanumeric character display)
y
y
LeD indicators (Red, Green, Amber)
y
y
LCD Description
Alarm, Supervisory and Trouble conditions display applicable condition, status and circuit for each correlating condition
y
y
Environmental Specifications
Mount indoors only.
y
y
Temperature 32° to 120°F, humidity 93% non-condensing.
y
y
verify panel is properly grounded.
y
y
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make
y
y
all cable entries from the sides, bottom, or rear of the cabinet. verify that they will not interfere with the batteries or other
components.
The panel and system must be tested and maintained in accordance with all local and national codes and ordinances.
y
y
System Configurations / Appliances
System Configurations / Appliances
Table 2:
Model
Description
Local
Auxiliary
Remote
Station
Central
Station
Proprietary
PFC-6800
Main Board/Panel Assembly
Y
Y
Y
Y
Y
CA-6500
Class A expander
O
O
O
O
O
UD-1000
DACT
N
N
Y
Y
Y
RA-6500 or
RA-6075
LCD type remote Annunciator
O
O
O
O
O
PSN-1000 or
PSN-1000(E)
Intelligent Power Supply expander
O
O
O
O
O
SLCE-127
SLC Loop expander
O
O
O
O
O
LeD-16
LeD Annunciator
O
O
O
O
O
DRv-50
LeD Driver
O
O
O
O
O
RLY-5
Relay expander
O
O
O
O
O
FCB-1000
Fire Communications Bridge
O
O
O
O
O
FIB-1000
Fiber Interface Bridge
O
O
O
O
O
SPG-1000
Serial/Parallel Printer Gateway
O
O
O
O
O
3005013
end of line resistor assembly
Y
Y
Y
Y
Y
3005012
end of line resistor and diode
N
Y
N
N
N
Y = Yes, required for applicable section
N = No, not required for applicable section
O = Optional, may or may not be used, has no affect on the applicable section.