PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17
11
To edit/rename an entry, select the field you would like to change using the arrow keys as done when setting up the software
zones. Press “Enter” to open the field. Once the field is available, scroll through the available characters to find the letter,
number, or special character desired using the Up/Down arrow keys. Move to the next character space using the left/right
arrow keys. When finished, press “Enter” to save changes before pressing “ESC”.
When selecting the order the points are listed in, the screen will allow you to change the number through either the up/down
arrow keys or by manually typing in the order number preferred. All single digit number selections must use a zero. It is
highly recommended that the assigned point name and number is written down to avoid confusion and programming errors.
When selecting a Point Function, use the up/down arrow keys to select a function for the notification or signaling circuit.
The options for the output (NAC) circuits are:
• City Tie
• Aux Door Holder Low AC (Aux D-Hold-AC)
• Aux Door Holder (Aux D-Hold)
• Aux Resettable
• Aux Constant
• Wheelock Sync
•
System Sensor Sync (Sys Sensor)
• Gentex Sync w/T4
• Gentex Sync
•
AMSECO Sync
•
NAC Gen Purp
• Unused
Zone Name
NAC 1
Select Point:
Current: 1
Set: [
1
]
NAC 1
Point Function
Curr: NAC Gen Purp
Set: [
City Tie
]
The options for the input circuits are:
• Smoke
• HVAC Restart
•
Supervisory
•
CO Alarm
• Lamp Test
• Disable Inputs/Outputs
• Disable Outputs
• Disable Inputs
• Fire Alarm
•
Silence
•
Reset
• Aux Input
• Trouble Monitor
• Fire Drill
• Tamper
• Waterflow
•
Pull Station
• Heat
• Unused