PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17
Section 4: Programming Options
The control panel is configured using the built in keypad. The panel stores the site specific configuration data in
non-volatile memory.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
Topic
Feature or
Option
Permitted
in UL
(Y/N)
Possible Settings
Setting(s)
Permitted
in UL864?
Comment
Misc
Idle LCD Message
Y
Yes/No
All Settings Allowed
Misc
Display Events
Y
Initial Event
Newest Event
Initial Event
Auto display of
first event
Misc
SLC Blink
Y
Normal/Slow/Off
All Settings Allowed
Misc
Alarm Verification
Time
Y
0-60 Sec
All Settings Allowed
Misc
Waterflow Delay
Y
0-255 Sec
All Settings Allowed
Misc
AC Report Delay
Y
30 Minutes to 30 Hours
1-3 Hours
For UL864 use
1-3 Hr
Misc
DH Low AC
Dropout Delay
Y
No delay, 15 Sec, 1 minute,
5 minute
All Settings Allowed
Misc
Autotest Time
Y
Time of Day
All Settings Allowed
Misc
Autotest Interval
Y
1-24 Hours
All Settings Allowed
Misc
Strobes Active
When Silenced
Y
Yes/No
All Settings Allowed
Misc
50 Hz AC
Y
Yes/No
All Settings Allowed
Misc
CO Tone on
Annunciators
Y
Yes/No
All Settings Allowed
Misc
Low Temp Events
Are Supervised
Y
Yes/No
All Settings Allowed
Misc
Disable 24 hours
PZT Resound
Y
Yes/No
No
Misc
Display AM/PM
Y
AM/PM, 24 Hour
All Settings Allowed
Misc
Synchronize to
Network Time
Y
Yes/No
All Settings Allowed
Misc
SNTP Server
Y
North-America.Pool.NTP.
org
All Settings Allowed
Misc
Time Zone
Y
24 Time Zone Selections
All Settings Allowed
Misc
DST Enabled
Y
Yes/No
All Settings Allowed
Misc
DST Start
Y
Month/Day
All Settings Allowed
Misc
DST End
Y
Month/Day
All Settings Allowed
6