INSTALLATION
GUIDE
SET THE DIP SWITCHES
ON THE ADJUSTMENT BOARD
DESCRIPTION
ON
OFF
1
Closed Door Force
Additional force applied while door is in closed
position. Be sure to maintain ANSI compliance
if using on low energy application. Cannot
exceed 30 lbf to get door moving from jamb.
Disabled (Default)
2
Push / Pull Arm
Slide Arm Application. Operator stroke at 90
°
degrees or less. Visible change in performance
may not always be noticeable.
Push Arm Application. Operator stroke 90
°
or
greater. (Default)
3
Night Function (Exit
Only)
Allows for one final activation at input 10 when
On-Off switch is in OFF (night function)
position.
Disabled. The On/Off switch, when OFF, requires
manual operation of the door. (Default)
4
Push and Go
Enabled
Disabled (Default)
5
Full Power / Low
Energy
Low Energy performance enabled. 5 seconds to
open, 7 seconds hold open, 5 seconds to close.
Speed & time potentiometers are disabled.
Settings are fixed.
Disabled. Control can be adjusted for full power or
low energy operation via potentiometers. (Default)
6
Lockout Function
Overhead presence sensor input (17) is
inhibited during closing cycle unless input 14 is
triggered. Connect COM and Input 14 to NC
output of lockout safety beam.
Disabled. Overhead presence sensor input (17) is
inhibited during closing cycle. Otherwise, if
commanded, it keeps an open door open and a
closed door closed. A command at Input 14 will stall
the door. (Default).
7
Inhibit at 30 Degrees
Before Door Fully
Open
Input is disabled at 30 degrees prior to full
open door position. Eliminates need for
external inhibiting switch.
Stall function remains un-inhibited for full door
stroke. (Default)
8
Power Close
Additional closing force applied for final 10
degrees of closing.
Disabled (Default)
9
Assisted Manual
Closing
***
Enabled assisted closing following a manual
opening
Disabled assisted closing following a manual opening
10
FACTORY USE ONLY
***
PORTALP USA, Inc. recommends the use of a door-mounted secondary activation device when dip switch 9 is
ON - Enabled.
WWW.PORTALP.COM
|
27
Automatic Doors & Building Access Control
SW10
(Full Power) & S
W19
(Low Energy)