INSTALLATION
GUIDE
SET-UP
PROCEDURES
Perform a setup at the control as follows:
§
Ensure main power is on
§
At the I/O control board, depress the SW1 button for approximately 5 seconds. When the red LED (LD2) at the Adjustment Board
begins flashing rapidly, release the button. The blue LED will continue flashing.
§
Door will slowly go open, recycle partially, close and then re-open.
§
Do not interrupt the process and do not move the door manually during this time.
§
If the door does not open and the red LED (DL2) is flashing slowly, check to make sure the motor is plugged in properly at the control
board. Correct as necessary.
§
Once the setup process is complete, the door will close and the LED will go out.
§
Setup is complete.
IMPORTANT NOTE:
If the operator stroke is altered in any way, a re-learn must be accomplished.
§
Upon completion of the Setup, activate the door to open and ensure all performance is acceptable.
§
Adjust opening and closing speed, as necessary. If speeds are changed, a re-learn is not required.
§
A re-learn is not required following a main power recovery.
§
Adjust hold-open time as required.
§
Additional adjustments are available through the TAP.
B1
– Battery – use CR1216 battery – required to
maintain timer settings and date programmed
by the TAP
TR1
– Opening speed adjustment
TR2
– Closing speed adjustment
TR3
– Hold-open time adjustment
TR4
– Closing speed adjustment when power is
OFF
TR4
will only be enabled when jumper
J6 is moved to the correct pins. (it is enabled
by default).
J2
– USB port
J4
– Ribbon cable connector between boards
J5
– Motor Connector
J7
– Power supply connector between boards
SW1
– “Parameter Changed” button
SW2
– 10 Position “Functions” Dip Switch
For adjustments beyond those mentioned
herein, use the TAP. See TAP Users Guide
for additional information.
WWW.PORTALP.COM
|
24
Automatic Doors & Building Access Control
SW10
(Full Power) & S
W19
(Low Energy)