MPK with CommandPak

 Control System BACnet /IP User’s Guide

•  5 – Supply air CFM
•  6 – Exhaust air CFM
•  7 – Purge air CFM
•  8 – Outside air CFM
•  9 – Supply fan current signal
•  10 – Exhaust fan current signal
•  11 – Purge fan current signal
•  13 – Pool 1 temperature
•  14 – Pool water circuit A pressure drop
•  15 – Pool 2 temperature
•  16 – Pool water circuit B pressure drop
•  19 – Air off evaporator temperature
•  20 – Air off evaporator humidity
•  22 – Evaporator bypass damper position feedback
•  24 – Outside air damper position feedback
•  25 – Recirc air damper position feedback
•  26 – Space pressure
•  27 – Return air CO2 level
•  28 – Surface temperature
•  29 – Outside air filter pressure drop
•  30 – Return air filter pressure drop

UNIT FAULT CODE AND LAST UNIT FAULT CODE (XWIUNITGNLFLTCODE)

AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit. The last fault (AV1022) 
indicates the most recent previous fault condition for the unit. The value for these objects is decoded as follows:

•  0 – Normal
•  1 – Coil freeze warning active
•  2 – Fire trip mode active
•  3 – Smoke purge mode active
•  4 – Supply fan not running
•  5 – Exhaust fan not running
•  6 – Purge fan not running
•  7 – Exhaust fan VFD fault active
•  8 – Supply fan VFD fault active
•  9 – Purge fan VFD fault active
•  10 – System startup active Normal for 5 minutes after power on.
•  11 – Supply fan deadheaded. Supply fan requested on with both outside air and recirc air dampers less than  

       25% open.

•  12 – Aux heating system failure
•  13 – Aux cooling system failure
•  14 – Compressor Module 1 fault active
•  15 – Compressor Module 2 fault active
•  16 – Compressor Module 3 fault active

Содержание MPK series

Страница 1: ...DOCUMENT SVW07 MPKBACNIP 20171020 UPDATED OCTOBER 2017 PoolPak MPK with CommandPak Control System CPCS BACnet IP User s Guide...

Страница 2: ...advanced password of 9995 then press Enter 6 Use the arrow keys to scroll down to BAS Interface then press Enter 7 Press the Enter key to move the cursor to different fields Use the arrow keys to chan...

Страница 3: ...the following address in a web browser http IP Address config where IP Address is the address assigned to the card manually or through a DHCP server The computer used must be on the same subnet as th...

Страница 4: ...side Air RH AV R 14 xwfOutAirTmp Outside Air Temperature C AV R 15 xwfOutAirVol Outside Air Volume CFM AV R 16 xwfOutDprFbk Outside Air Damper Position AV R 17 xwfPool1WtrTmp Pool1 Water Temperature C...

Страница 5: ...1ModeReq Cmpr1 Mode Requested Stages AV R 1018 xwiCpr2ModeReq Cmpr2 Mode Requested Stages AV R 1019 xwiCpr3ModeReq Cmpr3 Mode Requested Stages AV R 1020 xwiDehStgRqd Dehumidification Stages Rqd Stages...

Страница 6: ...Modes Requested are enumerated values indicating the operation mode of the corresponding compressor system The present value for these objects can be decoded as follows 0 Compressor Off 1 Air Heating...

Страница 7: ...ressure drop UNIT FAULT CODE AND LAST UNIT FAULT CODE XWIUNITGNLFLTCODE AV1022 and AV1024 are enumerated values indicating a general fault condition for the unit The last fault AV1022 indicates the mo...

Страница 8: ...resented by integer values in degrees Fahrenheit CONTROLLING OCCUPANCY MODE The BAS can control the dehumidifier s Purge mode directly This control overrides all internal schedules and controls except...

Страница 9: ...uested set point change is outside of the acceptable range Select set points based on the acceptable range 3491 Industrial Drive York Pennsylvania 17402 USA 800 959 7725 Fax 717 757 5085 2017 PoolPak...

Отзывы: