T200A Hardware Operation Manual
38
5.4.2 Ratio test
Connect I1 output to the CT primary side and CT secondary side to the current
measuring terminal, shown as above figure. Don’t make open circuit.
Select the
Ratio 250A
menu, shown as above figure.
Set the current for output, and CT secondary current rating. The software will
calculate the ratio by the CT secondary current rating automatically.
Press the
Run
button to output current. The tester will display the current it has
measured and the ratio that has been calculated.