5.4 CT Test:
5.4.1 Primary side injection
Connect wires as above figure, and connect the I1 output into the CT primary
side
Select high power AC current menu, shown as above figure.
Select a appropriate current output range
Set the current value for output
Press the
Run
button to output current, check the sampling of protection, or
action behaviors of relay and switching.
If the output current has insufficient power, the overload lamp will flame and the
output will be shut down at the same time.