5.3.8 Directional test
This function can be realized in the AC test of Pick Up.
This unit can make the boundary for power direction relay.
Connect wires as above figure shown.
Select high precision AC test menu as above figure shown.
Set amplitude and phase of voltage/current in the non-action zone of power
direction relay.
Press the
Run
button to output voltage and current values. Change the phase to
make the phase angle of voltage/current move from the non-action zone to the
action zone. During the protection acting period, mark the boundary I; then
change the moving direction of phase, which is also moving from non-action
zone to action zone, then marks the boundary II during the protection acting
period. Thus, calculate the sensitive angle with these measuring boundaries I
and II by the software automatically.