NF802 Intelligent Relay Tester User Manual
17
Configuration process: Press
to enter into shortcut setting window→ Select module in
module list→ Press
→ Configure to the related shortcut buttons.
The tester can be controlled by PowerTest in external PC, while selecting "Connect to PC".
: Window minimization
: System set and IEC configuration, it is going to introduce the detailed configuration
method for SMV and GOOSE.
Press “
” in the main interface. It pops up the “System & IEC” interface or press “
”
in the test page. Before testing, set the system parameters according to the test object. In
the Type column, users can choose “Digital output” or “Analog output”. When choosing
“Digital output”, the “SMV”, “GOOSE subscription” and “GOOSE publish” are activated.
Choose the protocol required: IEC61850-9-2(Ed1.0),IEC61850-9-2(Ed2.0), IEC61850-9-1,
IEC60044-8(SG)
,
SIMENS
, Low Signal,
ECT/EPT (XJ), ECT/EPT (SG), and
IEC60044-8(NARI)
. When the protocol is low signal, and the analog output channel is low
level analog output (Ua’,Ub’,Uc’,Uz’,Ia’,Ib’,Ic’,Iz’), users should set the PT ratio and CT ratio
as well. While choosing “IEC61850-9-2”, the primary parameter is default. Users should set