11
P9
Weekend (second house)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Mo
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Tu
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
We
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Th
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Fr
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Sa
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Su
Measured
Temperature
Precision:
0.1°C
Environmental
Operating Temperature:
0°C - 40°C
Shipping and Storage
Temperature:
-10°C to +50°C
Setting Temperature
Range
Comfort, Reduced:
5°C to 35°C
by 0.5°C step
Holiday (Antifreeze):
7°C
10°C (adjustable):
0.5°C to 20°C
Timer:
5°C to 35°C
Regulation
Characteristics:
Hysteresis of 0.5°C
Electrical
Protection:
Class II - IP30
Power Supply:
2 AAA LR03 1.5V
Alkaline
Operating Life:
2 Years
Output:
2 Points Contact
(Free Contact)
Relay 5 Amps 250Vac
Optional External
Sensor:
10k ohms at 25°C
9. Technical details
10. Fault Diagnostics
My thermostat doesn’t start
Battery
- Check if the protection sticker
Problem
on the batteries is removed.
- Check the orientation of the batteries.
- Check the charge of the batteries.
My thermostat LED, blinks in red
Problem
The logo blinks (ambient sensor)
on Sensors
- Contact your installer.
The logo blinks (floor sensor).
- Check the connection
of the sensor.
- Disconnect the sensor, and check
it with an ohmmeter (the value
must be around 10kohms).
Battery
The logo blinks (batteries)
level is low
- Replace the batteries.
My thermostat seems work correctly but
the temperature in the room was never
in accordance with the program
Program
- Check the clock.
- Check the difference between
Comfort and Setback temperature
is not too high?
- Contact your installer, to check
and adjust the calibration.
8. Pre-set
Programs (9)