User Manual - PolyGard
®
CO SPC-1110
Page
4
PolyGard
is a registered trademark of MSR
SPC1110I01
Phone (858) 578-7887 & (888) GO IN
TEC
Fax (858) 578-4633 & (888) FX IN
TEC
Specification subject to change without notice.
IN
TEC
Controls, Inc., P.O. Box 12506, La Jolla, CA 92039
www.inteccontrols.com
Printed in USA 040401
Manual override of low alarm relay
Manual switch for “Auto” or “On” function of the relay 1K1 (R1)
Switch position:
Auto
= alarm relay 1K1 normal operation
On
= alarm relay 1K1 manually on
Caution!
Replacement sensor elements, which are not bias types, are shipped with a tiny spring of wire shorting the sensor
and reference electrodes.
This spring MUST BE REMOVED prior to installing the element into the sensor assembly.
Optional Display
3.5 digits display of concentration
LED power:
green
Power on, and normal operation
red
Failure
operation
LED alarm:
orange
Low alarm level active
red
Low
and
high
alarm
level
active
Button “Reset 2
nd
Alarm”
Reset high alarm, when relay is set to latched
Button “Reset Audible”
Reset internal horn and relay R3 for remote alarm
Optional time delay relay for low alarm
Time delay relay for delayed activation of relay 1K1
RTE-P11 analog timer
= on-delay, adjustable from 0.1 min to 10 min