7 Troubleshooting
7.1 Diagnostics
Trouble Reason
Solution
Power not applied
Measure power on terminal block X1
terminal H / N for 120 VAC (24
Fuse failure
Check miniature fuses 1F1, 1F2 or F1 on
motherboard
Interruption in the cable
connection between motherboard
and displayboard
Check cable connections for tight fit
No indication of power
(opional with display),
and/or
test button does not
function
Failure on displayboard
Replace displayboard
Mode operating switch S1 on
displayboard, position 3 = OFF
Set switch in position:
1 = low trip/setpoint
2 = high trip/setpoint
4 = sensed value
Interruption in the cable
connection between motherboard
and displayboard
Check cable connections for tight fit
No indication value at
digital display
Failure on displayboard
Replace displayboard
Interruption in the cable
connection between motherboard
and displayboard
Check cable connections for tight fit
Sensor sensitivity too low
Replace sensor
Cannot calibrate
sensorboard
Failure on sensorboard
Replace sensorboard
Trip/setpoint values are set too
high
Adjust trip/setpoint values again
(see section 5.1 to 5.3)
Cannot set trip/setpoints
Failure on motherboard
Replace motherboard
Interruption of sensor cable or
sensor sensitivity too low
Check cable connection, or if necessary
replace and calibrate sensor
Fail-safe alarm
Control span voltage lower then
200mV
Recalibrate the sensor, or if necessary
replace sensor element