5.5 Motherboard jumper selection table
Function
Element
Factory
Set
1-5 VDC signal for external use
X
1-5 VDC not used
X
Jumper JP1
Relay R3 will be active with low alarm
X*
1
Jumper
JP3
Relay R3 will be active with high alarm
X*
1
Jumper
JP4
Relay R3 will be not active
X*
1
Jumper
JP5
System failure also activates high alarm
X
System failure does not activate high alarm
X
Jumper JP9
High alarm without latch function
1-2
High alarm with latch function
2-3
Jumper JP12
With optional digital display
X
Without optional digital display
X
Jumper JP2
Switching differential of low trip/setpoint, 4%
1-2
Switching differential of low trip/setpoint, 10%
2-3
Jumper JP6
Switching differential of high trip/setpoint, 4%
1-2
Switching differential of high trip/setpoint, 10%
2-3
Jumper JP8
Internal function
X
Jumper JP7*
2
Internal function
2-3
Jumper JP10*
2
Internal function
1-2
Jumper JP11*
2
Note:
*
1
Only one of the three jumpers can be installed.
*
2
Do not change the factory jumper position setting.
5.6 Displayboard jumper selection table
Function
Element
Factory
Set
Display value without sign +/-
X
Jumper JP1.1
Display value with sign +/-
X
Jumper JP1.2
Button “Reset 2 (high) alarm” enabled
X
Button “Reset 2 (high) alarm” disabled
X
Jumper JP12
Internal function
X
Jumper JP7
1
1
Do not change the factory jumper position setting