A service person must verify that all socket outlets from which the equipment is
to be powered provides a connection to the building protective earth.
To verify, use a suitable long test/wander lead with an ohm meter/multimeter.
Connect one end to a known protective earthing point of the building electrical
installation and ensure that there is a reading of less than one ohm to each
earthing contact of all socket outlets to be connected as shown in
.
Socket Outlets Earthing Contact Points
If lack of protective earth is discovered at any of the socket outlets, this must first
be rectified by installing a suitable protective earthing conductor in accordance
with local wiring code and regulations. This must be carried out by a registered,
competent electrician.