Polycom RealPresence Immersive Studio User Guide
Regulatory Information
System Rating
31
To disconnect the room lighting from the AC mains supply, turn off the switch labeled
(lighting disconnect).
Instructions for installer: A readily accessible disconnect device shall be incorporated
external to the equipment. Electrician needs to install a single throw double pole switch
within a one meter area of the Lighting Controller. Service to the single throw double
pole switch should not be greater than 20 amps. The warning label must be placed on
the switch that says “VIDEOCONFERENCE ROOM LIGHTING DISCONNECT.”
A disconnect device shall have a contact separation of at least 3mm. Vertically
mounted disconnect switches and circuit breakers shall be mounted so that the UP
position of the handle is the “on” position.
The main electronics are stationary pluggable equipment Type A with simultaneous
multiple connections to the AC mains supply.
●
The building installation must provide a means for connection to protective earth.
●
The equipment must be connected to that means.
WARNING: HIGH LEAKAGE CURRENT. EARTH CONNECTION
ESSENTIAL BEFORE CONNECTING SUPPLY.