DIAGNOSTICS
REMOVAL OF MALFUNCTIONS
The drives do not react to the
control commands from the
remote control device
Limited remote control device range
-
Check the remote control device battery (see
“Replacement of the
remote control device
battery”).
-
Check the antenna of the control module
(cables, location, see page
30).
-
Make sure that there are no external element
causing interference in the flow of radio waves
(electric pole, reinforced wall, etc.). In such case it
is necessary to envisage an independent antenna.
Remote control device that is not stored in
the memory
Store in the remote control device memory (see
page
40).
Drive are not connected properly
Check the drive cables (see pages 14, 31-32).
The
status light of the
control module is off
Electronic control system in standby mode
Press the
for 2 seconds in order to wake the
electronic control system.
The electronic control system is not powered
-
Check the mains power supply.
-
Check the power supply cable.
The
status light of the control module is flashing:
1 flash
Functioning with power supply from the spare
battery
Check the mains power supply.
2 flashes
The drive is in standby mode, awaiting for
beginning of the automatic learning
Launch the automatic learning of the gate travel
path (see page 34).
3 flashes
Damaged photocells
-
Make sure there is no obstacles between
photocells.
-
Check the photocell settings.
-
Check the photocell cables (see pages 14, 42-
43).
-
If the photocells have been disconnected on
purpose, perform the “Deactivation of automatic
closing” procedure, page 39.
4 flashes
The “START” control of the electronic module
is activated all the time (terminals 5-6)
Check the accessories connected to the
“START”
of the electronic module.
5 flashes
The thermal protection of the electronic
system is activated
Wait for the electronic system to cool down, until
the moment the
status light becomes
continuously lit again.
6 flashes
Short-
circuit in the “BUS” of the electronic
module (terminals 3-4)
Check the accessories connected to the “BUS” of
the electronic module.
Short-
circuit in the “24 V” of the electronic
module (terminals 7-9)
Check the accessories connected to the “24 V” of
the electronic module.
Short-
circuit within the “orange light” of the
electronic module (terminals 8-9)
Check the cables of the orange light (see page 43).
Short-circuit within the drive
Check the drive cables (see pages 14, 31-32).
7 flashes
Electronic malfunction
Contact the technical support department of
Somfy.
The gate opens again after it
finishes closing
Loose the wing brackets and move them slightly
towards the centre of the gate.
Diagnostics
Содержание EASY WAY PACK 201
Страница 1: ...Manual EASYWAYPACK 201 AUTOMATIC GATE INTELLIGATE smart gate ...
Страница 4: ......
Страница 66: ...My account This sheet includes the information provided during the activation of Connexoon SMART GATE ...
Страница 74: ...Name the product and then click OK The product will appear on the list then SMART GATE ...
Страница 78: ......