![PMA KS 40 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/pma/ks-40/ks-40_interface-description_1569321007.webp)
KS KS KS
CODE Description
40 50 90
Disp
R/W Len. Value
range
Rem.
51
2nd set-point or
f f f
SP2
R/W
9
SPL
...
SPH
/- - - -
#>
52
Set-points for programmer
f f f
SP3
R/W
9
SPL
...
SPH
53
f f f
SP4
R/W
9
SPL
...
SPH
54
Segment times for programmer
f f f
Pt2
R/W
7
0...9999
55
f f f
Pt3
R/W
7
0...9999
56
f f f
Pt4
R/W
7
0...9999
57
5th set-point (programmer)
f f f
SP5
R/W
9
SPL
...
SPH
58
5th segment time (progr.)
f f f
Pt5
R/W
7
0...9999
59
Gradient
f f f
Gr
R/W
8
0.1...999.9 /- - - -
>
q
61
Configuration level
f f f
Con1
R
7
q
62
f f f
Con2
R
7
q
63
-
f f
Con3
R
7
q
64
- -
f
Con4
R
7
71
Correcting variable for start-up
-
f f
YA
R/W
6
5...100
72
Set-point for start-up
-
f f
SPA
R/W
9
SPL
...
SPH
73
Holding time for start-up
-
f f
PtA
R/W
7
0...9999
74
Max. correct. variable average
-
f
-
YH
R/W
6
5...100
75
Limit for averaging (corr. var.)
-
f
-
LYH
R/W
7
0.1...10.0
76
2nd correcting variable
- -
f
Y2
R/W
6
YLL
...
YLH
77
Filter time constant
- -
f
tF
R/W
8
0.0...999.9
78
Span start
f f f
InL
R/W
9
999...(
InH
- 1)
y
79
Span end
f f f
InH
R/W
9
(
InL
+ 1)...9999
y
81
Decimal point
f f f
dP
R/W
4
(dP)
<
82
Lower set-point limit
f f f
SPL
R/W
9
InL
...(
SPH
- 1)
83
Upper set-point limit
f f f
SPH
R/W
9
(
SPL
+ 1)...
InH
85
Lower output limit
- -
f
YLL
R/W
7
-100...(
YLH
- 10)
86
Upper output limit
- -
f
YLH
R/W
7
(
YLL
+ 10)...100
87
Cycle time heating
f f f
t1
R/W
8
0,4...999,9
88
Cycle time cooling
f f f
t2
R/W
8
0,4...999,9
89
Operation locking
f f f
Loc
R/W
4
(Loc)
<
B2,01
Set-points
SP2
...
SP11
- -
f
R/W 80/83
SPL
...
SPH
Ü
B2,02
Segment times
Pt2
...
Pt11
- -
f
R/W 60/63 0...9999
Ü
Ü
Block access (
Ä
chapter 3.1, General structure and chapter 6, Communication examples)
*
KS 40 / KS 50: (Y) can be read only.
KS 90:
Y
can be read and written. The written value becomes valid in manual mode.
Ö
The process value is only valid, if bit 3 and bit 5 in status byte 1 are 0 (no sensor or polarity error).
ä Ä
chapter 7, Remote/Local operation
#
With KS 40 / KS 50 positioners: output signal (–100%) / 0%...100%, no switch-off function.
<
The limits of these values depend on the instrument (
Ä
data sheet or operating instructions).
>
If four minus signs are transmitted, the relevant function is switched off.
y
These values can be written only with standard signal input. They must not be changed with running
programmer or ramp (
Ä
NAK).
English
CODE table
960612
5
Interface description 9499 040 47701