background image

0000110982/231018/A SER 

EN - 11

DISPOSAL

After life of the product, dispose it of in accordance with state 

or local regulations.

PRESSURE LOSS CALCULATION

The fall of pressure in a air duct system or in a hose is mainly 

determined by the air velocity in that system.

The higher the velocity is, the higher the pressure loss will be. 

And the higher the pressure loss is, the less air the fan will 

extract. See 

fig. 7.1

 for a Pressure Loss Chart to identify a 

suitable fan regarding the relationship between airflow and 

pressure loss.

In a ventilation system with many extraction devices and long 

suction ducts, you can minimise pressure loss by increasing 

the size of the ducting. This will also ensure even velocity 

throughout the system. 

Hose diameter

Length

A

Ø 100 mm (4 in.)

7,5 m (24.7 ft)

B

Ø 100 mm (4 in.)

10 m (33 ft)

C

Ø 100 mm (4 in.)

12,5 m (41 ft)

D

Ø 125 mm (5 in.)

7,5 m (24.7 ft)

E

Ø 125 mm (5 in.)

10 m (33 ft)

F

Ø 125 mm (5 in.)

12,5 m (41 ft)

G

Ø 150 mm (6 in.) 

7,5 m (24.7 ft)

H

Ø 150 mm (6 in.)

10 m (33 ft)

I

Ø 150 mm (6 in.)

12,5 m (41 ft)

J

Ø 200 mm (8 in.)

10 m (33 ft)

Note: 75 mm (3 in.) hoses are not available in North America.

A

B

C

D

E

F

G

H

I

J

Airflow Volume: General Guidelines

Vehicles serviced

m

3

/h  

(cfm)

Hose

diameter

 

Automobile / Motorcycles

460-510 
(270-300) 

Ø 100 mm (4 in.)

Trucks (Public Works, 
Rental Fleets, etc.)

850-935
(500-550)

Ø 125 mm (5 in.)

Heavy Duty Trucks

1100-1360 
(650-800)

Ø 150 mm (6 in.)

Off-Road (Constr., 
Compressor Tests, etc.)

1700-2400 
(1000-1400)

Ø 200 mm (8 in.)

When 1200 to 1350 m

3

/h is needed, Plymovent recommends a 

150 mm (6 in.) hose. A 200 mm (8 in.) hose can be used for 

larger applications, as it supports larger engines operating 

under load. For those cases, the exhaust flow and temperature 

increase dramatically.

Air velocity in ducting: 17,8 - 22,9 m/s (3500 to 4500 fpm). 

The chart below shows the pressure loss in the hose reels a 

different airflows. Refer to the Airflow Volume: General 

Guidelines table below for the vehicle, airflow and hose 

diameter guidelines. The curves show these combinations of 

hose reel/hose diameter/hose length (uncoiled position).

We recommend that you confirm existing exhaust 

temperatures to ensure proper hose, fan and 

airflow selection. 

Fig.7.1   Pressure loss chart

Содержание ER-650-100

Страница 1: ...www plymovent com SER EN Spring Operated Exhaust Hose Reel...

Страница 2: ...s responsibility to ensure they have attained the most recent copy of this document for their files The instructions in this publication only serve as a guideline for installation use maintenance and...

Страница 3: ...SER EN 1 TABLE OF CONTENTS ENGLISH Page Preface 1 Introduction 3 2 Product description 4 3 Safety 5 4 Installation 6 5 Maintenance 10 6 Disposal 11 7 Pressure loss calculation 11 8 SER Spare parts 12...

Страница 4: ...or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particulate i...

Страница 5: ...springs that are factory installed to the outside of the reel assembly an operator pulls the hose down to a convenient position which locks the hose in place when no longer needed the operator recoils...

Страница 6: ...d must not be opened Be careful when servicing the SER product If you have any questions about the content in this manual please contact Plymovent or your Plymovent authorised distributor Be careful w...

Страница 7: ...perator connects the nozzle and when the hose is no longer needed the operator pulls down on the hose to release the ratchet lock and guides the hose back to its rest position which is determined by t...

Страница 8: ...made aware that a quarter turn of the hose should always remain on the drum as shown in fig 4 2 2a If the hose is pulled down completely the entire hose is removed from the drum and the recoil mechan...

Страница 9: ...7 in I 489 mm 19 2 in 489 mm 19 2 in 489 mm 19 2 in 489 mm 19 2 in 590 mm 23 2 in Hose length Mounting height Maximum reach 7 5 m 25 ft 3 m 9 8 ft 6 2 m 20 4 ft 3 5 m 11 5 ft 5 9 m 19 4 ft 4 m 13 1 ft...

Страница 10: ...racket Insert bolts and tighten slightly Slide the bracket up and down parallel to the A frame center to align with the hose reel outlet Tighten bolts to ensure the unit is properly secured C Unfold t...

Страница 11: ...om arm Mount spiro tubing and hose on the boom arm E Mount ducting bend to hose reel then mount the hose to the ducting bend F Readjust friction as needed G Fig 4 3 3a Mounting bracket for EB 3 5 EB 4...

Страница 12: ...equalise the spring tension if the spring still functions Unscrew all socket head cap screws at the spring casing C Mark the position of the spring casing Put the new spring casing in position Tighte...

Страница 13: ...I 150 mm 6 in 12 5 m 41 ft J 200 mm 8 in 10 m 33 ft Note 75 mm 3 in hoses are not available in North America A B C D E F G H I J Airflow Volume General Guidelines Vehicles serviced m3 h cfm Hose diam...

Страница 14: ...com click the Contact Plymovent link and then click Sales Offices CE Declaration CE declaration of conformity for machinery We Plymovent Koraalstraat 9 1812 RK Alkmaar the Netherlands herewith declar...

Страница 15: ...www plymovent com 0000110982 231018 A SER...

Отзывы: