THE CONTROLLER WITH BALANCED VENTILATION FUNCTION 

ecoVENT MIDI 

 

FOR CONTROLLING VENTILATION CENTRAL WITH MECHANICAL RECUPERATOR 

 

 

 

   
 

 

 
 
 

 
 
 
 
 

 

 

 
 

 
 
 
 
 
 
* is not a standard controller equipment. 

 
INSTALLATION AND OPERATING MANUAL

 

ISUUE: 1.3_EN 
SOFTWARE VERSION: 03.xx

 

 

 

simTOUCH2 

ecoTOUCH 

12-2019 

 

GHE 

ecoPRESS EX1* 

ecoNET300* 

www.econet24.com 

ecoNET.apk 

 

Содержание ecoVENT MIDI

Страница 1: ...IDI FOR CONTROLLING VENTILATION CENTRAL WITH MECHANICAL RECUPERATOR is not a standard controller equipment INSTALLATION AND OPERATING MANUAL ISUUE 1 3_EN SOFTWARE VERSION 03 xx simTOUCH2 ecoTOUCH 12 2...

Страница 2: ...llation etc check if the controller is not connected to the mains Installation should be done by a person with appropriate electrical qualifications Improper cables connection could result in the cont...

Страница 3: ...S 28 12 THE CONTROLLER INSTALLATION 28 12 1 MOUNTING OF CONTROL PANEL 28 12 2 MAIN MODULE INSTALLATION 30 12 3 CLEANING AND MAINTENANCE PROCEDURES 31 12 4 ELECTRICAL CONNECTION 32 12 5 ELECTRICAL SCHE...

Страница 4: ...parameters may result in emergency state Modification of preset parameters should be done only by person familiar with manual Device software does not provide high security level against false install...

Страница 5: ...rmation about documentation The controller manual is a supplement for the recuperator manual In particular except for this manual the recuperator manual should also be observed The controller manual i...

Страница 6: ...6...

Страница 7: ...7 USER MANUAL ecoVENT MIDI...

Страница 8: ...nsor Exhaust sensor Panel sensor Panel address User modes Mode 1 Mode 2 Mode 3 Mode 4 Air supply Exhaust preset temp GHE GHE settings Auto Close Open Summer opening temp Winter opening temp Regenerati...

Страница 9: ...ure Air supply fan speed Exhaust fan speed Schedules Schedules support Schedule Preset temperature Preset temperature Control leading sensor Air supply sensor Exhaust sensor Panel sensor Panel address...

Страница 10: ...een has been used to control the device Settings change is done using rotary menu Selection and edit in the menu is done by pressing desired symbol on the screen Grouped parameters from the selected m...

Страница 11: ...he Stand by mode In this mode it displays the current date and time external temperature and information Recuperator turned off To start the controller press anywhere on the screen then the following...

Страница 12: ...een with options to read information and change selected parameters 1 Settings for main mode and user modes 2 Additional mode selection 3 Main menu access 4 Information field e g Active alarms press t...

Страница 13: ...eding the demand for expenditure change threshold SAP signal from the fire control unit ECO signal from the alarm central TR1 primary heater thermostat trip TR2 secondary heater thermostat trip 11 Ext...

Страница 14: ...temperature outside 15 Information ALARM alarm signaling operation of the primary heater secondary heater operation cooler operation 16 Position of the bypass actuator 17 Position of the mixer chamber...

Страница 15: ...preset temperature value this mode can be applied e g during the presence of large number of people in the room Airing mode amends exhaust fan expenditure while turning off air supply fan this mode c...

Страница 16: ...the efficiency of heat recovery system resistance e g against air filter dirtying exchanger resistances change due to humidity or dirt starting air flow via ground heat exchanger The function turn on...

Страница 17: ...is cooled to preset temperature using air from the outside 7 10 Alarm central Settings related to supporting signal from alarm central After receiving signal from the alarm central the fans expenditu...

Страница 18: ...nge set the schedule activation Start Stop parameters hours and minutes and select the active operation mode Mode parameter Icon allows to copy currently defined schedule to any day of the week Res ic...

Страница 19: ...reen saver mode can select the screen saver mode for Off On or Clock ecoNET settings a WiFi network configuration in case of connection an internet module ecoNET300 to the controller Enter SSID networ...

Страница 20: ...20...

Страница 21: ...data Installation ventilation scheme Data history graph The following is the appearance of the website and the mobile application for remote operation of the ventilation system with exemplary work pa...

Страница 22: ...adline Filter dirty operating period expired contact service Filter might be dirty call service to replace filters Signaling alarm no display of energy recovery Until new inspection date is entered by...

Страница 23: ...LARM output active Continually since the occurrence of the cause of the alarm After alarm acceptance filter replacement procedure starts Air supply filter dirtying call service Possible air supply fil...

Страница 24: ...ill immediately lower fans speed It will provide lowering the amount of outdoor air intake resulting in successive increase of CO2 concentration When CO2 concentration in the air reaches nominal value...

Страница 25: ...25...

Страница 26: ...26 INSTALLATION AND SERVICE SETTINGS ecoVENT MIDI...

Страница 27: ...E temp sensor 6 GHE 7 GHE throttle actuator 8 primary electric or water heater with thermostat NO NC 9 bypass throttle actuator 10 bypass 11 exhaust temp sensor 12 extraction fan 14 cross flow or rota...

Страница 28: ...according to actual demand Anti freezing protection exchanger is realized depending on recuperation central configuration by reducing heat recovery with the help of bypass throttle or by heating up th...

Страница 29: ...current taken by controller only Overall power consumption depends on devices connected to the controller transport Do not use the controller under steam condensation conditions protect from water Sto...

Страница 30: ...room panel 2 vent holes to provide air circulation During panel removal figure below to take out panel 1 from the housing insert flat elements 2 into indicated slots This will cause housing catches t...

Страница 31: ...screwdriver into the indicated slots This will bend the catches 4 of the panel housing and allow the panel to be removed 1 12 2 Main module installation The controller s module must be developed The d...

Страница 32: ...fastened 1 so that accidental falling out of one of the wires could not cause a hazard 12 3 Cleaning and maintenance procedures The outer surface and maintenance of the control panel screen Keep safe...

Страница 33: ...can cause fire electrocution or damage to the device It is not allowed to use damaged power supply cable plug or loose electric outlet Ignoring above recommendations may lead to electrocution or fire...

Страница 34: ...ndary heater thermostat Normally closed Analog inputs AIN1 pressure for air supply analog CO2 sensor analog humidity sensor AIN2 pressure for extraction Relay outputs 230 VAC W1 air supply fan W2 exha...

Страница 35: ...35 The controller allows free outputs configuration depending in used ventilation central The electrical diagram shows default outputs configuration...

Страница 36: ...only with ecoPRESS IN1 differential pressure sensors Using different sensor types is forbidden Sensors should be placed on the module board at marked place Pressure Sensor 1 and Pressure Sensor 2 by...

Страница 37: ...central permission to operate turning off the central from menu level by operator or SAP alarm If any from above conditions occur then attempt to start procedure is done at full hour For testing time...

Страница 38: ...o No modification requests 0x06 and 0x10 will be blocked Recuperator control permission to control with Modbus if parameter is set to No controlling the controller from Modbus level will be disabled 1...

Страница 39: ...allows value modification of many registers containing current values of parameters Request frame includes looking at the beginning of the frame address of requested device 1 byte requests 1 byte in c...

Страница 40: ...40 0 0 0 integer 999 sensor failure 11 10 Trec GHE temperature T5 O 40 0 40 0 0 0 integer 999 sensor failure 12 11 Theat Temperature behind secondary heater T1 O 40 0 40 0 0 0 integer 999 sensor failu...

Страница 41: ...0 20 integer Unit C 42 41 Temp_USER 3 Preset temperature in USER 3 mode I O 8 30 20 integer Unit C 43 42 Temp_USER 4 Preset temperature in USER 4 mode I O 8 30 20 integer Unit C 44 43 W1 Air supply fa...

Страница 42: ...r activation SM1 I O 0 1 0 integer 0 inactive 1 active 74 73 SM1_Limit Opening limit of mixing chamber actuator SM1 I O 0 100 100 integer Unit 75 74 BMS_adress Device address for BMS communication O 0...

Страница 43: ...0 50 integer Unit Pa 106 105 Pressure_W2 _USER3 Preset pressure exhaust user 3 mode I O 0 4000 50 integer Unit Pa 107 106 Pressure_W2 _USER4 Preset pressure exhaust user 4 mode I O 0 4000 50 integer U...

Страница 44: ..._T4_ AL Sensor T4 malfunction O 0 1 0 integer 0 inactive 1 active 130 208 Sensor_T5_ AL Sensor T6 malfunction O 0 1 0 integer 0 inactive 1 active 131 209 Sensor_T6_ AL Sensor T5 malfunction O 0 1 0 in...

Страница 45: ...y Dirt testing hour Dirt test override Manual control Air supply and exhaust control Control type Standard Constant pressure Constant expenditure Information IN1 IN2 input settings IN1 IN2 inputs work...

Страница 46: ...pport Device blockade support Inspection counter reset Days till inspection Day till blockage Device unlocking password Default settings Default setting panel Default setting service Default setting c...

Страница 47: ...Filter class Initial resistance Final resistance Dirt alarm Central emergency mode Medium class as above Accurate class as above Filter classes default settings yes no Exchanger anti freezing Exchange...

Страница 48: ...1 6 Default settings Default setting panel Default setting service Default setting client Counters erase Access passwords change Installer Password Service password Recuperator operation signal mode N...

Страница 49: ...s parameter allows to set delay providing time to change throttles settings Dirt test adjustment in V parameter allows setting voltage controlling fans during tests Detection mechanism when choosing T...

Страница 50: ...expenditure Air quality sensor Settings related to support of digital air quality sensor Sensor logical state logical state of digital air quality sensor Fans velocity fans velocity after digital air...

Страница 51: ...ion is displayed Amount of days till blockage Setting amount of days after which device operation will be blocked Device unlocking password Setting a password by installer to unlock device Device bloc...

Страница 52: ...o full open of mixer actuator Primary heater Primary heater manufacturer settings Heater Kp settings Setting amplification of the PID algorithm for water and electric heater Heater Ki settings Setting...

Страница 53: ...igured by installer Functions available for installer Settings available for installer Filter classes parameters Timed mechanism Detection by pressure switches Pressure difference transducers Dirt tes...

Страница 54: ...fan convector operation mode Fan convector heating cooling To properly configure fan convector function settings in service menu must be also amended In sub menu GHE Mixer chamber Cooler settings choo...

Страница 55: ...l filter classes testing procedures parameters and their starting periods e g delay time and tests adjustment parameters day and hour of test to start dirt test adjustment has identical value in Volts...

Страница 56: ...56...

Страница 57: ...57 Assembly dimensions of the MIDI module...

Страница 58: ...58...

Страница 59: ...59...

Страница 60: ...60...

Страница 61: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Database No 000009381...