42
58
57
Speed_W2_
USER4
Speed of W2 in
USER 4 mode
I/O
dyn.
(25)
dyn.
(100)
50
integer
Adjustment in %
59
58
Speed_W2_
ECO
Speed of W2 in
ECO mode
I/O
dyn.
(25)
dyn.
(100)
50
integer
Adjustment in %
60
59
-
-
-
-
-
-
-
61
60
DATE_day
Day
I/O
1
31
1
integer
62
61
DATE_month
Month
I/O
1
12
1
integer
63
62
DATE_year
Year
I/O
15
99
16
integer
64
63
TIME_hour
Hour
I/O
0
23
1
integer
65
64
TIME_minut
es
Minute
I/O
0
59
1
integer
66
65
Stop_time_E
CO
Periodic pause
time in ECO mode
I/O
1
24
1
integer
Unit: hours
67
66
Work_time_
ECO
Airing time in ECO
mode
I/O
0
100
10
integer
Unit: minutes
68
67
Filter_time_r
emaining
Time remaining to
replace filters
O
0
999
1500
integer
Unit: day
69
68
Service_time
_remaining
Time remaining to
general inspection
O
0
999
90
integer
Unit: day
70
69
GWC_Enable
GHE operation
permition
I/O
0
2
1
integer
0 - closed,
1 - auto,
2 - open
71
70
GWC_Winter
GHE turn on upper
threshold
–
winter
I/O
5
20
8
integer
Unit: °
C
72
71
GWC_Summ
er
GHE turn on lower
threshold
–
summer
I/O
10
30
18
integer
Unit: °
C
73
72
SM1_Enable
Mixing chamber
activation (SM1)
I/O
0
1
0
integer
0
–
inactive,
1 - active
74
73
SM1_Limit
Opening limit of
mixing chamber
actuator (SM1)
I/O
0
100
100
integer
Unit: %
75
74
BMS_adress
Device address for
BMS
communication
O
0
256
1
integer
76
75
-
-
-
-
-
-
-
77
76
BMS_change
_en
BMS settings
change
O
0
1
1
integer
0
–
turn off,
1
–
turn on
78
77
BMS_STOP_
en
BMS START_STOP
O
0
1
1
integer
0
–
turn off,
1
–
turn on
79
78
-
-
-
-
-
-
-
80
79
UID1
UID - characters 1
and 2
O
12336
23130
-
ASCII
81
80
UID2
UID - characters 3
and 4
O
12336
23130
-
ASCII
82
81
UID3
UID - characters 5
and 6
O
12336
23130
-
ASCII
83
82
UID4
UID - characters 7
and 8
O
12336
23130
-
ASCII
84
83
UID5
UID - characters 9
and 10
O
12336
23130
-
ASCII
85
84
UID6
UID - characters
11 and12
O
12336
23130
-
ASCII
86
85
UID7
UID - characters
13 and14
O
12336
23130
-
ASCII
87
86
UID8
UID - characters
15 and 16
O
12336
23130
-
ASCII
88
87
UID9
UID - characters
17 and 18
O
12336
23130
-
ASCII
89
88
UID10
UID - characters
19 and 20
O
12336
23130
-
ASCII
90
89
UID11
UID - character 21
O
48
90
-
ASCII
Younger byte is
a mark, omit
older byte
91
90
P1_value
Measured pressure
–
air supply
O
0
4000
0
integer
Unit: Pa
92
91
P2_value
Measured pressure
–
exhaust
O
0
4000
0
integer
Unit: Pa
93
92
Flow1_value
Measured flow
–
air supply
O
0
4000
0
integer
Unit: m3/h
Содержание ecoVENT MIDI
Страница 6: ...6...
Страница 7: ...7 USER MANUAL ecoVENT MIDI...
Страница 20: ...20...
Страница 25: ...25...
Страница 26: ...26 INSTALLATION AND SERVICE SETTINGS ecoVENT MIDI...
Страница 56: ...56...
Страница 57: ...57 Assembly dimensions of the MIDI module...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Database No 000009381...