Outputs
configuration
and
confirmation of configuration
19
The controller allows configuration of active
functions on relay outputs and analog
outputs.
Additionally the installer or manufacturer
must confirm the correctness of outputs
configuration. Without confirmation, the
following alarm is activated: R
ecuperator
settings error, possible settings deletion,
and
the recuperator will not work. After applying
installer and manufacturer settings, confirm
settings correctness by choosing
Yes
in the
Confirm service/manufacturer configuration
parameter of the controller to allow its
operation.
19.1
Outputs configuration for fan
convector
Fan convector is a device with functionality of
both cooler and secondary heater. Controller
has software modules installed, which allow to
control such devices. To turn on fan convector
support go to
Manufacturer menu.
Under sub-
menu
Analog outputs change
and change any
function on digital output to
Fan convector.
Such modification will delete settings of
outputs 0
–
10 V, that are connected with
cooler and secondary heater control, and will
assign settings of abovementioned devices to
fan convector. From sub-menu
Relay outputs
settings
it is possible to define additional
signals controlling fan convector: signal
permitting its operation
–
Fan convector
operation
–
and signal selecting fan convector
operation
mode
–
Fan
convector
heating/cooling.
To properly configure fan convector function
settings in service menu must be also
amended.
In
sub-menu
GHE/Mixer
chamber/Cooler settings
choose
Cooler
support
parameter and set it to
Yes.
Then, in
sub-menu
Heaters
change
Secondary heater
t
ype
parameter to
Analog water or Analog
electric.
Keep in mind, that functions
protecting secondary heater remain active
and depending on the selected heater type the
controller will act differently after thermostat
output is activated. In case of secondary
water heater soaking process will start. In
case of electric heater an operation blockade
of secondary heater will activate. Decision of
which heater should be used is made by
person configuring the system.
Fan convector function does not have its own
settings, when cooling is needed the controller
cooler settings are used, while heating is
needed the declared secondary heater
settings of controller are used. Controllers
settings can be amended in relevant sub-
menus in Manufacturer menu.
20
Software update
Software update can be performed using only
microSDHC memory card, inserted into the
socket in control panel housing.
Before making the electric connection of
outputs, make sure that their configuration is
correct.
Operation permission signals and fan
convector mode selection signals must be
mandatorily declared if they are required by
device manufacturer.
Incorrectly defined settings may cause fan
convector malfunction or lower heating
comfort in ventilated rooms.
Содержание ecoVENT MIDI
Страница 6: ...6...
Страница 7: ...7 USER MANUAL ecoVENT MIDI...
Страница 20: ...20...
Страница 25: ...25...
Страница 26: ...26 INSTALLATION AND SERVICE SETTINGS ecoVENT MIDI...
Страница 56: ...56...
Страница 57: ...57 Assembly dimensions of the MIDI module...
Страница 58: ...58...
Страница 59: ...59...
Страница 60: ...60...
Страница 61: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl National Waste Database No 000009381...