![pleasant hearth PH35PS Series Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/pleasant-hearth/ph35ps-series/ph35ps-series_owners-manual_1567637031.webp)
7077-801D • September 17, 2019
31
F. Through The Wall
Horizontal termination cap must be a minimum of 6
inches. (152mm) from the wall. Approved for mobile home
installations. Must use 3 or 4 inch (76-102mm) “L” or “PL”
listed pellet venting or Listed double wall pipe and an
authorized Outside Air Kit in mobile homes.
NOTE:
In Canada, where passage through a wall or
partition of combustible construction is desired,
the installation shall conform to
CAN/CSA-B365
NOTICE:
Please note that while the minimum clearance
for the termination cap is 6 inches (152mm)
there is the possibly of soot build-up around
the termination area. If this occurs we suggest
to move the termination further away from the
house to prevent it. The suggested minimum
is 12 inches.
Wall
Thimble
Illustration shows venting going in both directions.
Choose which one is best for your installation.
3 in. (76mm)
Minimum
3 in.
(76mm)
Minimum
6 in (152mm) Minimum
6 in (152mm)
Minimum
6 in.
(152mm)
Minimum
Non-combustible Hearth Pad
Wall
Thimble
Horizontal
Termination
Cap
10 in.
(254mm)
Minimum
6 in.
(152mm)
Minimum
From Glass
DO NOT DOWNWARD VENT.
The following will occur:
•
The appliance will not vent properly
•
Smoke spillage in the house
•
Excessive sooting
CAUTION
Straight Out
45 Degrees