44
Installation and user guide PLATINUM Inverter 7000 R3, 9000 R3, 11000 R3, 14000 R3, 16000 R3
Technical data
Interfaces
... R3
DC input
Multi-Contact MC4
DC isolation device
Switch integrated in inverter for isolation from
generator field
Reverse voltage protection (DC)
Yes
AC output
Spring terminal
PLATINUM network
EIA 485, 2 x RJ45 Western Modular, add. plug
with screw terminals
Service interface
EIA 232, SubD 9-pole socket
Ambient conditions
... R3
Operating temperature range
–20 °C to +60 °C
Max. temperature for rated power
+45 °C
Storage temperature
–25 °C to +80 °C
Max. humidity
95 %
Protection class
IP65 in accordance with DIN EN 60529
Contamination level
II, external and internal use possible
Inverter data
... R3
Dimensions (H x W x D)
629 x 547 x 290 mm
Weight
45 kg
Switching concept
Transformerless, DIVE, RACE,
ENS in accordance with VDE 0126-1-1
Cooling concept
Convection cooling
Protection class / overvoltage
protection
I / III
Overvoltage category
DC side: II
AC side: III
Optical display
Full graphic LCD, 170 x 76 pixels
Integrated datalogger
Storage capacity sufficient for operating time of
30 years
The technical data is valid for a maximum height of 2,000 m above sea
level.