Installation and user guide PLATINUM Inverter 7000 R3, 9000 R3, 11000 R3, 14000 R3, 16000 R3
Installation
CAUTION
Destruction of the inverter!
f
Never mix up the phases with PE or N.
Prepare the connection cable for the AC voltage
Dimensioning the wire cross section is the responsibility of the
electrician and depends on the cable length and installation situation.
▪
Min. cross section 4 mm
2
▪
Max. cross section 16 mm
2
1. Secure the three-phase AC voltage connection lines accordingly; see "Technical data"
on page 42.
2. Strip 18 mm of insulation from the AC voltage connection lines and add wire-end
sleeves.
Connection
6
1. Unfasten the AC screw connection (6)
with seal from the underside of the
inverter.
2. Direct the prepared AC voltage
connection line through the AC screw
connection and seal.
3. Feed the AC voltage connection line
into the housing from below.
4. Tighten the AC screw connection.