The control panel may be installed in the same housing where the gas cylinder is installed, however one has
to remember that the housing cannot be airtight and the gas cylinder needs to be placed minimally 1,5 metres
away from the source of fire. The housing needs to have an upper ventilation slot above the top of the bottle
(of an area min 1/100 of the area of the base of the housing) and a lower ventilation slot (of an area min 1/50
of the area of the base of the housing). The dimensions of the housing may vary to accommodate different
types and dimensions of the gas cylinders however they also have to be sufficient for hassle-free installation
of the gas cylinder. Control panel montage above the gas cylinder is not recommended as it would impede its
hassle-free installation and replacement.
WARNING!!!
• After making sure that the device has been correctly installed acquaint yourself with the attached User’s Manual.
• Only after acquainting yourself with the User’s Manual and correctly attaching the gas linkage may you start the
device.
• If in future a need arises of having to take the insert out of the housing it may only be done when the device is turned
off and cooled down and the valve on the gas cylinder is closed.
• Keep this instruction manual for the lifetime of the device.