Copyright Planika Sp. z o.o.
www.planikafires.com
IG0098#01
19.02.2018
13
•
The optional housing for the gas cylinder cannot be airtight and has to be correctly ventilated. The housing
needs to have an upper ventilation slot above the top of the bottle (of an area min 1/100 of the area of the
base of the housing) and a lower ventilation slot (of an area min 1/50 of the area of the base of the housing).
The dimensions of the housing may vary to accommodate different types and dimensions of the gas cylinders
however they also have to be sufficient for hassle-free installation of the gas cylinder.
4.2.2
Control panel montage in a separate storage
The control panel along with the gas valve connected with the insert through elastic linkage may be installed away
from the housing for the GaLiO Insert. It can be placed maximally within a 1 metre radius from the centre of the device.
•
Before placing the insert into the housing the control panel needs to be placed in an easy-to-reach spot
allowing convenient control of the device and, if necessary, quick shutdown and cut-off of gas supply. The
control panel may be installed in a horizontal or vertical position with the use of angles attached to it.