Copyright Planika Sp. z o.o.
www.planikafires.com
IG0150#05
29.06.2020
20
4.3.5.
Flame height directly to maximum position
Pressing the
„+“
button twice automatically
decreases the flames to the HIGH position
Press and hold
„+“
button to increase the flame
level and to turn on the burner from the stand-by
position.
NOTE:
If you turn on the burner by pressing the
button, it must ignite within 10 seconds. If this
does not happen, immediately close the gas tap
and warn the fitter.
4.3.6.
Automatic Turn Down To Pilot
3 Hour No Communication Function
The valve will turn to pilot flame if there is no communication between handset and receiver for a 3 hour period. The
fire will continue to function normally when communication is restored.
Receiver Overheating
•
Powered by mains adapter: The valve turns t
o pilot flame if the receiver temperature is higher than 176 °F
(80 °C). If batteries are installed in the receiver in this configuration the temperature must not exceed 60 °C.
•
Powered by batteries and/or connected to the V module: The valve turns to pilot position if the temperature
in the receiver is higher than 140 °F (60 °C).
NOTE:
When the receiver temperature is below 140 °F (60 °C), the main burner can be turned ON manually.
4.3.7.
Automatic Shut Off
Countdown Timer
At end of countdown time period, the fire shuts off. The Countdown Timer only works in Manual, Thermostatic, and
Eco Modes. Maximum countdown time is 9 hours and 50 minutes.
Low Battery Receiver
With low battery power in the receiver the system shuts off the fire completely. This will not happen if the power
supply is interrupted.