Alarm 1
Reset
Type of Reset for contact
of alarm 1.
(Automatic Reset)Default
(Manual Reset)
(Manual Reset Stored)
26
Alarm 1 State
Error
State of contact for alarm
1 output in case of error
Default
27
Alarm 1 Led
Defines the state of the
OUT2 led corresponding
to the relative contact
Default
28
Alarm 1
Hysteresis)
Alarm 1 hysteresis
-999…+999 digit
∗
(tenths of degree if temperature).
Default: 0.
29
Alarm 1 Delay
Alarm 1 delay
-180…+180 Seconds
Negative: delay in alarm output
phase.
Positive: delay in alarm entry phase.
Default: 0.
30
Alarm 1
Setpoint
Protection
Alarm 1 set protection.
Does not allow user to
modify setpoint
Default
31
Alarm 2
Alarm 2 selection.
Alarm intervention is
associated with AL2
(Disabled) Default
(Absolute Alarm)
(Band Alarm)
(High Deviation Alarm)
(Low Deviation Alarm)
(Absolute Command setpoint Alarm)
(Start Alarm)
(Cooling)
(Loop Break Alarm)
32
Alarm 2 State
Alarm 2 output contact
and intervention type
(n.o. start) Default
Normally open, active at start
∗
The display of the decimal point depends on the setting of parameter
and parameter