24
1009
Relay status (0=off, 1=on)
Bit 0 = relay Q1
Bit 1 = relay Q2
Bit 2 = reserved
Bit 3 = SSR
RO
0
1010
Heating output percentage
(0-10000)
RO
0
1011
Cooling output percentage
(0-10000)
RO
0
1012
Alarms status (0=none, 1=active)
Bit0 = Alarm 1
Bit1 = Alarm 2
RO
0
1013
Manual reset: write 0 to reset all alarms.
In reading (0=not resettable, 1=resettable):
Bit0 = Alarm 1
Bit1 = Alarm 2
WO
0
1014
Error flags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold junction error
Bit3 = Process error (sensor)
Bit4 = Generic error
Bit5 = Hardware error
Bit6 = L.B.A.O. error
Bit7 = L.B.A.C. error
RO
0
1015
Cold junction temperature (tenths of degree)
RO
?
1016
Start/Stop
0=controller in STOP
1=controller in START
R/W
0
1017
Lock conversion ON/OFF
0=Lock conversion off
1=Lock conversion on
R/W
0
1018
Tuning ON/OFF
0=Tuning off
1=Tuning on
R/W
0
1019
Automatic/manual selection
0=automatic ; 1=manual
R/W
0
1020
TA current ON (Ampere with tenths)
RO
?
1021
TA current OFF (Ampere with tenths)
RO
?
1022
OFF LINE
1
time (milliseconds)
R/W
0
1023
Instant Current (Ampere)
RO
0
1
If value is 0, the control is disabled. If different from 0, it is the max. time which can
elapse between two pollings before the controller goes off-line.
If it goes off-line, the controller returns to Stop mode, the control output is disabled
but the alarms are active